background image

N24 Installation Manual

4

5

 

Zone Inputs (TB3)

The inputs for activating the outputs of the N24 board. The 

usage of these inputs varies based on the settings of the DIP 

switches – see DIP Switch settings for more information 

(item 10).

•  INxA 

EOL (Class B) or (Class A)

•  INxB 

EOL (Class B) or Return – (Class A)

•  INxC 

Input -

•  INxD 

Input +

(See input example wiring diagrams for details on Page 4.) 
These terminals are not supervised by the N24 board -  

supervision of these terminals and the entire input loop is 

performed by the FACP.

These terminals are removable and accept wire sizes from 
AWG14-AWG22.

bk 

Configuration DIP Switches (SW3)

These switches configure the operation of the N24 board. 
Note that Switches 1 and 2 MUST be ON

 

when using any of 

the Output Synchronization Protocols.
Refer to the chart below for settings:

b 

FlexIO Connection

This connector supplies the fault and FAI status between the 

FPO power supply system and the N24 board. The appropriate 

cable is supplied with the N24 board. See the FPO power supply 

manual for more information.

b 

Input Power LED

This LED indicates that power is available at the input of the 

N24 board. If this LED is not lit, check the Input Fuse of the 
N24 and voltage at the B1/B2 power input.

b 

Status LEDs

These LEDs indicate the status of the N24 board as follows:

IN1 / IN2 

Light RED when a valid signal is received at 

the corresponding input terminals. These 

LEDs may flash if a coded input is applied 

to the respective input.

OUT1 - OUT4

 

Light YELLOW if a fault is detected on the 

corresponding output terminals. Faults 

detected include open, short, or overcurrent.

COMFLT

 

Lights YELLOW if any fault condition 

is detected by the N24 board. Faults 

 

detected include open or shorted outputs, 

output overcurrent, and invalid Dip switch  

configurations.

N24 – Accessory Overview

Switch Number

1 2 3 4 5 6 7

Input Configuration

IN1 controls all outputs

Off Off

IN2 not used
IN1 controls all outputs

Off On

IN2 controls all outputs
IN1 controls OUT1 and OUT2

On Off

IN2 controls OUT3 and OUT4

Use this setting when using an  

Output Synchronization Protocol setting

On On

IN1 controls strobes
IN2 controls horns

 (only when IN1 is also active)

Output Wiring  Configuration

Four Class B Outputs (OUT1, 2, 3, 4)

Off Off

Two Class A Outputs (OUT1-2 & OUT3-4)

Off On

Two Class B (OUT1, 2)  

and One Class A Output (OUT3-4)

On Off

One Class A Output (OUT1-2) and Two Class 

B Outputs (OUT3,4)

On On

Output Protocol Configuration

Steady (follower mode) on OUT1 and 2

Off Off Off

ANSI Temporal Code on OUT3 and 4
ANSI Temporal Code on OUT1, 2, 3, 4

Off Off On

Gentex Synchronization Protocol

Off On On

Wheelock Synchronization Protocol

On Off On

AMSECO/Potter Synchronization Protocol

On On Off

Summary of Contents for FlexPower N24

Page 1: ...LifeSafety Power Inc PH 888 577 2898 TechSupport LifeSafetyPower com P03 027 Rev A08 N24 Installation Manual...

Page 2: ...A or Class B Maximum output is 3A per output zone The N24 is powered from a 100W or larger FPO power supply set for 24VDC The N24 works either as a follower passing along synchronization or audible c...

Page 3: ...correspond with the B1 and B2 power inputs See the Specifications section of this manual for fuse type and ratings 5 NAC Output Terminals TB1 TB2 The NAC outputs of the N24 board The outputs are confi...

Page 4: ...ese LEDs indicate the status of the N24 board as follows IN1 IN2 Light RED when a valid signal is received at the corresponding input terminals These LEDs may flash if a coded input is applied to the...

Page 5: ...N1 or IN2 D In from FACP C B A IN1 or IN2 D In from FACP C B A Polarities shown in Alarm Condition Polarities shown in Alarm Condition EOL EOL EOL values as required by FACP IN1 or IN2 D In from FACP...

Page 6: ...ribed in this manual Verify that the correct EOL is installed on Class B Outputs for Class A outputs verify that the output loop returns to the N24 board properly Verify that no shorts opens or high i...

Page 7: ...n the Specifications section of this document Q 1 Ensure proper configuration of all jumpers and switches Q 2 Apply AC power to the FPO power supply and connect the battery set Verify that no yellow L...

Page 8: ...maintenance instructions for the FPO Series power supply system DC1 DC1 DC2 DC2 BR BR FPO switch set for 24V FPO FPO FlexIO connection FlexIO connection FlexIO FlexIO B1 B2 BR IN1 IN2 A B C D A B C D...

Page 9: ...FPO FlexIO connection FlexIO connection FlexIO connection FlexIO connection FlexIO FlexIO B1 B2 BR IN1 IN2 A B C D A B C D FlexIO B1 B2 BR N24 OUT4 OUT3 OUT2 OUT1 FACP without synchronized outputs Cla...

Page 10: ...n LifeSafety Power makes no warranties as to the accuracy or completeness of the information and disclaims any liability regarding its use LifeSafety Power s only obligations are those in the LifeSafe...

Reviews: