Example:
This is an example for determining the airflow in a 6 in. (0.5 ft) duct.
•
The Pitot tube reading was 0.025 inches of water. From the chart, this is 640 ft/min.
The 6 in. (0.5 ft) duct has a cross sectional area of:
A =
πr
2
= [πd
2
] / 4
A = [3.14 x (0.5 ft)
2
] / 4
A = 0.2 ft
2
The airflow is then: (640 ft./min.) x (0.2 ft
2
) = 128 cfm
For your convenience, the cross sectional areas of some common duct sizes are listed below:
DUCT. DIAM.
(inches)
CROSS SECTION AREA
(sq. ft.)
5 (127 mm)
0.14
6 (152 mm)
0.20
7 (178 mm)
0.27
The accuracy of the air flow reading will be affected by how close to any elbows or bends the readings are
taken. Accuracy can be increased by taking an average of multiple readings as outlined in the literature
supplied with the Pitot tube.
Note:
Place pitot tube a minimum
of 18” from blower or elbows
Note:
Duct connections may
vary, depending on model.
Summary of Contents for 1500E-ECM
Page 1: ......
Page 10: ...www lifebreath com 4 DIMENSIONAL DRAWINGS 1500I ECM Dimensions 1500E ECM Dimensions ...
Page 11: ...www lifebreath com 5 DIMENSIONAL DRAWINGS 2000IFD Dimensions 2000EFD Dimensions ...
Page 12: ...www lifebreath com 6 DIMENSIONAL DRAWINGS 2500IFD Dimensions 2500EFD Dimensions ...
Page 39: ...www lifebreath com Page 20 WIRING DIAGRAMS 1500I ECM E ECM ...
Page 40: ...www lifebreath com Page 21 WIRING DIAGRAMS 2000IFD EFD 208 ...
Page 41: ...www lifebreath com Page 22 WIRING DIAGRAMS 2000IFD EFD 208SP ...
Page 42: ...www lifebreath com Page 23 WIRING DIAGRAMS 2000IFD EFD 460 ...
Page 43: ...www lifebreath com Page 24 WIRING DIAGRAMS 2000IFD EFD 575 ...
Page 44: ...www lifebreath com Page 25 WIRING DIAGRAMS 2500IFD EFD ...
Page 45: ...www lifebreath com Page 26 WIRING DIAGRAMS 2500IFD EFD 208 ...