![Lifebreath 1500E-ECM Installation Manual Download Page 16](http://html1.mh-extra.com/html/lifebreath/1500e-ecm/1500e-ecm_installation-manual_1909112016.webp)
www.lifebreath.com
10
W
EATHERHOODS
Outside Weatherhoods:
•
The 1500E-ECM, 2000EFD, and 2500EFD units are shipped with 2 weatherhoods inside the cabinet which
attach to the outer edge of the cabinet using the bolts provided. The weatherhoods have built-in screens
to prevent foreign objects from entering in the ductwork through the outside hoods.
•
The 1500I-ECM, 2000IFD, and 2500IFD require weatherhoods to be built elsewhere and provided by the
contractor.
Recommended:
o
no less than 10 ft. (3 m) apart from each other
o
at least 18 in. (46 cm) above snow line or ground level
o
away from sources of contaminants, such as automobile exhaust fumes, gas meters, garbage cans,
containers, etc.
o
not exposed to prevailing winds
o
mesh screen with 1/4 in. (6.35 mm)
o
the outside perimeter of the weatherhood must be caulked to prevent leakage into the building.
o
the design and size of the weatherhoods or louvers chosen by the installer must allow for adequate
free area. Water and debris penetration of the system is minimized when the airflow does not
exceed 750 FPM (3.81 m/s) free area velocity.
Ducting from the Weatherhoods:
•
Galvanized sheet metal ducting with sufficient cross section with an integral single piece vapor barrier
should be used to connect the HRV to the weatherhoods.
•
A minimum R value of insulation should be equal to 4 (RSI 0.75)
•
A good bead of high quality caulking (preferably acoustical sealant) and taping with a high quality
aluminum foil tape is recommended to seal the duct to both the HRV and the weatherhood.
Techgrilles:
•
The use of balancing dampers or adjustable grilles as supply air diffusers and air exhaust covers are
recommended. TECHGRILLES™ are round, efficient, sound absorbing devices available in 4”, 5”, 6” and 8”
(100, 125, 150, and 200 mm) models.
Part# 99-EAG4
4” diameter Techgrille
Part# 99-EAG5
5” diameter Techgrille
Part# 99-EAG6
6” diameter Techgrille
Part# 99-EAG8
8” diameter Techgrille
Attention
•
All ducting must meet UL Class 1 requirements.
•
Design and install the fresh air intake in an area where the hoods will gather the freshest air.
•
Do not use smaller mesh as it will be very susceptible to plugging up. Gravity dampers at the vents
must not be used as they will restrict air flow and often “seize up”.
Summary of Contents for 1500E-ECM
Page 1: ......
Page 10: ...www lifebreath com 4 DIMENSIONAL DRAWINGS 1500I ECM Dimensions 1500E ECM Dimensions ...
Page 11: ...www lifebreath com 5 DIMENSIONAL DRAWINGS 2000IFD Dimensions 2000EFD Dimensions ...
Page 12: ...www lifebreath com 6 DIMENSIONAL DRAWINGS 2500IFD Dimensions 2500EFD Dimensions ...
Page 39: ...www lifebreath com Page 20 WIRING DIAGRAMS 1500I ECM E ECM ...
Page 40: ...www lifebreath com Page 21 WIRING DIAGRAMS 2000IFD EFD 208 ...
Page 41: ...www lifebreath com Page 22 WIRING DIAGRAMS 2000IFD EFD 208SP ...
Page 42: ...www lifebreath com Page 23 WIRING DIAGRAMS 2000IFD EFD 460 ...
Page 43: ...www lifebreath com Page 24 WIRING DIAGRAMS 2000IFD EFD 575 ...
Page 44: ...www lifebreath com Page 25 WIRING DIAGRAMS 2500IFD EFD ...
Page 45: ...www lifebreath com Page 26 WIRING DIAGRAMS 2500IFD EFD 208 ...