background image

19

Drains

Connect the drain pans in the bottom of the HRV to a 
drain line  fastened  to  the  holes  provided.  Create  a  "P" 
trap  to prevent  odors  from  being  drawn  through.  Make 
sure  the drain  line  slopes  down  to  drain  properly  and  if 
this  is  not possible  a  condensate  pump  will  be  required 
for  removal of  the  water.  Note  that  stagnant  water  is  a 
leading  cause of  indoor  air  quality  problems;  confirm 
drainage  after installation  by  pouring  water  into  trays. 
Drain  line  must  be installed where it will not freeze.

The

 

Ductwork

 

System

A  well  designed  ducting  system  will  allow  the  HRV  to 
operate at its maximum efficiency. Avoid the use of 
under-sized ducting and sharp radius bends and tees 
which can significantly  increase  the  system  pressure 
drop  and reduce the air flows.
NOTE:  Fully  insulated  ducting  with  an  integral  vapor 
barrier  must  be  used  on  all  runs  passing  through 
unheated areas  in  order  to  avoid  condensation  problems 
and energy losses from the air streams.

* Consult

 

local

 

Codes

To  minimize  pressure  drop  and  noise,  galvanized  metal
ducts  sized  for  725  fpm  (3.68  m/s)  (maximum  velocity)
are recommended.  Keep  ducting  as  short  as  possible  and
use a  minimum  of  elbows  and  tees.  Connecting  sections
and shorter  runs  may  be  flexible  ducting  one  size  larger
than the  metal  duct.  Use  flexible  duct  connectors  at  the
HRV to avoid noise transmission.
All  duct  joints  must  be  secured  with  screws,  rivets  or 
duct  sealant  and  sealed  with  aluminum  duct  tape  to 
prevent leakage.

Outside

 

Weatherhoods

The  1500E-ECM  is  shipped  with  2  weatherhoods  inside 
the  cabinet  which  attach  to  the  outer  ends  of  the 
cabinet using  bolts  provided.  The  1500I-ECM  requires 
hoods  to be built elsewhere and provided by the 
contractor.
NOTE:  It  is  extremely  important  to  design  and  install 
the  fresh  air  intake  in  an  area  where  the  hoods  will 
gather the freshest air, free from restriction.

Recommended:

no less than 10 ft. (3 m) apart from each other

at least 18 in. (46 cm) above ground level

away  from  sources  of  contaminants,  such  as
automobile  exhaust  fumes,  gas  meters,  garbage
containers, cooling towers, etc.

not  exposed  to  prevailing  winds,  whenever
reasonably possible.

The  outside  perimeter  of  the  weatherhood  must  be 
caulked to prevent leakage into the building.
The  design  and  size  of  the  weatherhoods  or  louvers 
chosen  by  the  installer  must  allow  for  adequate  free 
area.  Water  and  snow  penetration  of  the  system  is 
minimized  when  the  airflow  does  not  exceed  750  FPM 
(3.81m/s) free area velocity.

Ducting

 

from

 

the

 

Weatherhoods

Galvanized  sheet  metal  ducting  with  sufficient  cross 
section  with  an  integral  single  piece  vapor  barrier 
should be  used  to  connect  the  HRV  to  the 
weatherhoods.  All ducting must meet ULC Class 1 Fire 
Rating.
A  minimum  R  value  of  insulation  should  be  equal  to 4 
(RSI 0.75), or as stated in local codes.
A  good  bead  of  high  quality  caulking  (preferably 
acoustical  sealant)  and  taping  with  a  high  quality 
aluminum  foil  tape  is  recommended  to  seal  the  duct  to 
both the HRV and the weatherhood.

Warm-side

 

Ducting

 

-

 

General

Ducting from the HRV to different areas within the 
building should be galvanized metal whenever possible.
To  minimize  airflow  losses  in  the  ductwork  system,  all 
ducts  should  be  as  short  as  possible  and  with  as  few 
bends  or  elbows  as  possible.  45Þ  elbows  are  preferred 
to  90Þ  elbows,  whenever  possible.  Use  Y  tees  instead 
of 90Þ tees whenever possible.
All  duct  joints  must  be  fastened  securely  and  wrapped 
with  a  quality  duct  tape  to  prevent  leakage.  We 
recommend aluminum foil tape.

Ducting

 

-

 

General

Summary of Contents for 1500E-ECM

Page 1: ...er operating at a higher static After installation the compatibility of the two pieces of equipment must be confirmed by measuring the airflows of the Heat Recovery Ventilator HRV by using the balancing procedure found in this manual It is always important to assess how the operation of any HRV may interact with vented combustion equipment ie Gas Furnaces Oil Furnaces Wood Stoves etc NEVER install...

Page 2: ...______________________________ Submitted by ____________________________________ DEFROST Factory set defrost time Supply motor is shut off while exhaust air defrosts core WEIGHT 460 lbs 210 kg SHIPPING WEIGHT 580 lbs 260 kg NOTE All specifications are subject to change without notice DIMENSIONS 1500I ECM in inches Specifications 1500I ECM TIMER OPTIONS 99 DET01 Lifebreath 20 40 60 Minute Timer Ini...

Page 3: ...haust air defrosts core WEIGHT 530 lbs 240 kg SHIPPING WEIGHT 650 lbs 290 kg TIMER OPTIONS 99 DET01 Lifebreath 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes 3 wire connection 20 gauge wire minimum 99 DET02 Lifebreath WIRELESS 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes Wirelessly connects to main control for ease of installation 4...

Page 4: ...ir defrosts core WEIGHT 530 lbs 240 kg SHIPPING WEIGHT 650 lbs 290 kg TIMER OPTIONS 99 DET01 Lifebreath 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes 3 wire connection 20 gauge wire minimum 99 DET02 Lifebreath WIRELESS 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes Wirelessly connects to main control for ease of installation 40 appro...

Page 5: ...OUTSIDE 5 The 1500E ECM E is designed for outdoor installations The duct connections for the Stale Air From Building and Fresh Air to Building ducts are at the ends of the unit The 1500E ECM is designed for outdoor rooftop installations The duct connections for the Stale Air From Building and Fresh Air to Building ducts are located at the bottom of the unit A roof curb is required for this install...

Page 6: ...ing the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After a few seconds the Dehumidistat light will either flash or be on continuous A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation A continuous light indicates the humidity level is lower than the setting Re...

Page 7: ... is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either flash or be on continuous A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation A continuous light indicates the humidity level ...

Page 8: ...the middle of the screw holes Refer to Figure B or C for placement 5 Cut in a 3 4 in by 1 in oval hole in the wall to allow for the wire opening and drill two 1 8 in holes for the screws and wall anchors Figure B or C 6 Pull 3 wire 20 gauge min 100 ft length max through the opening in the wall 7 Connect red green and yellow to the Wiring Terminals located on the Back Plate Figure B or C 8 Attach t...

Page 9: ...the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate to the Back Plate Figure B Note Be careful to correctly align the Face Plate to avoid damaging the Face Plate Contact Pins 10 Insert the Operating Instructions Card into the control Figure A 11 Connect the 3 wire 20 gauge min 100 ft length max to the digital controls terminal...

Page 10: ...essful repeat steps 1 6 When paired the DET02 Timers can be moved and installed elsewhere Estimated range of the Timer is 40 with no obstructions A RX02 Repeater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Turn on the main wall control by pressing the ON ...

Page 11: ...ess Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan operation The corresponding Status Light will illuminate under the number on the Timer to indicate either 20 40 or 60 minutes of HIGH speed fan operation To cancel the call for HIGH speed fan operatio...

Page 12: ... Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Status Light will illuminate and the unit will run on high speed ventilation for the selected time The High Speed Status Light will dim after 10 seconds of run time The High Speed Status Light will flash du...

Page 13: ...ard SPEED High R W Medium R Y Low R G JUMPER 13 Optional 20 40 60 Minute Timer Part 99 DET01 Boost unit to Ventilation Mode for 20 40 60 minutes no speed change Connect up to 4 maximum Connect to Yellow Red Green HIGH OFF OFF OFF MED LOW Optional 3 Speed Control Part 99 500 Connect to R W Y and G on Thermostat T18 T5 T13 C4 T17 T19 T1 T2 T3 T4 T6 T14 T15 T16 C3 C2 C1 RELAY Fan Hi Fan Med Fan Low F...

Page 14: ...um 115V 10 amp resistive load T30 T29 T28 T43 SPARE P2 P3 F2 MAX 2 amp R 24Vac Defrost Freeze K7 K1 K2 K8 T31 T32 T33 T34 T35 T36 T37 T38 T39 T40 T41 T42 Contact 1 N 0 COM N C N 0 COM N C N 0 COM N C N 0 COM Contact 2 Contact 3 Contact 4 N C Contact 2 and 4 These relays initiate whenever the HRV fans are operating ...

Page 15: ...oth sides 2 Remove first set of filters 3 Remove filter divider panels if only accessing from one side 4 Remove filters from behind filter divider panel 5 Replace all filters Ensure that filter divider panels are re inserted into unit Servicing Cores 1 Remove core service panel one or both sides 2 Slide cores out regular core maintenance 3 When placing the cores back into the unit ensure that ther...

Page 16: ...16 Option 1 Unit can be suspended with U channels and Threaded Rod Option 2 Mounting the 1500 Unit can be placed on blocks sleepers ...

Page 17: ...s under deck Securing the Frame To ensure proper mating with unit it is critical that mounting frame be squared to the roof as follows 1 With frame situated level in desired location on roof trusses tack weld one corner of frame 2 Measure frame diagonally from one corner to the opposite corner Repeat with the remaining two corners These dimensions must be equal for the frame to be square 3 It is e...

Page 18: ...LY TOP VIEW SIDE VIEW 14 356 mm 16 406 mm 19 483 mm 65 3 4 1670 mm 1 3 4 45 mm 1 3 4 45 mm 42 3 4 1086 mm 16 406 mm 19 483 mm 1 3 4 45 mm 1 3 4 45 mm STALE AIR RETURN FRESH AIR SUPPLY DUCT COLLAR SUPPORTS FACTORY INSTALLED PERIMETER WOODEN NAILER STRIP ...

Page 19: ...to be built elsewhere and provided by the contractor NOTE It is extremely important to design and install the fresh air intake in an area where the hoods will gather the freshest air free from restriction Recommended no less than 10 ft 3 m apart from each other at least 18 in 46 cm above ground level away from sources of contaminants such as automobile exhaust fumes gas meters garbage containers c...

Page 20: ...y isolated and separately grounded electrically from the air handler This will avoid a possible shock hazard to service people if a short to ground develops in one of the devices It may be necessary to install a separate fresh air supply ductwork system if the heating is other than forced air When installing an HRV the designer and installer should be aware of local codes that may require smoke de...

Page 21: ...ed directly into the ceiling space but this should occur near the air handler s intake By operating the HRV ERV on a 24 hour 7 day battery backed timer the unit can be set to operate only when occupancy or indoor conditions require the air exchange In installations where it is satisfactory to provide general exhaust from the space the air to be exhausted may be taken directly from the return air p...

Page 22: ...FWDEOH VSHHGV LJK PHGLXP DQG ORZ DFK RI WKHVH VSHHGV FDQ EH IXUWKHU DGMXVWHG WR REWDLQ WKH GHVLUHG DLUIORZ 7KLV LV GRQH RQ WKH 0 FLUFXLW ERDUG ORFDWHG ZLWKLQ WKH HOHFWULFDO ER RWK PRWRUV FRQWDLQ D VHSDUDWH 0 FLUFXLW ERDUG WR DOORZ IRU LQGHSHQGHQW DGMXVWPHQW RI WKH PRWRUV 7KH DGMXVW WDS ZLOO FKDQJH WKH DLUIORZV RQ DOO WKUHH RI WKH VSHHGV 3OHDVH QRWH WKDW WKLV XQLW KDV EHHQ IDFWRU VHW WR REWDLQ 0 DW...

Page 23: ...e unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a manometer capable of reading 3 digits of resolution The tube coming out of the top of the pitot is connected to the high pr...

Page 24: ...24 Wiring Diagram Neutral Neutre CHASSIS T44 Line Ligne C3 C2 C1 ...

Page 25: ...ndon Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labor required to install any replacement part s shall be dealt with at the option of the customer in either of the following ways a the customer may supply labor at their own expense or b if the product was purchased from a dealer then the dealer will supply labor at co...

Page 26: ...26 ...

Page 27: ...27 ...

Page 28: ...info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 1500 110116 ...

Reviews: