10

Optional 

Lifebreath 

Wireless Timer

 -

 

Part

 

#

99-DET02

ATTENTION

The 

W

ireless Timers and Repeaters must be 

matched to  the  main  wall  control  of  the  HRV

.

  

This process  is  called  "Pairing".  Multiple 
Timers  and Repeaters can be paired to a single 
wall control.

BC

02

 

Control

Press Simultaneously to 
Initiate Pairing Mode

Figure A 

Figure B

1/8 in hole for 
screw and 
anchor 

1/8 in hole 
for screw and 
anchor 

Break off tab

Alternate Wall Mount

1/8 in hole for 

screw and anchor 

Figure C

Back Plate 

Face Plate 

1/8 in 
hole for 
screw and 
anchor

Break off tab

Figure 

E

 

Figure 

D

DET02 Timer

20/40/60 Minute 
Status Lights 

Select Button 

initiates high speed 

ventilation for 20, 40 

or 60 min. 

Battery Indicator

Removable 

Backplate

The 

timer 

will 

override 

the 

operational 

mode 

(regardless  of  the  settings)  and  initiate  HIGH  speed 

Ventilation.  Upon  completion  of  the  timer  cycle,  the  HRV 

will  return  to  your  selected  operational  mode  and  speed 

setting. 
Initiates HIGH speed ventilation for 20, 40 or 60 minutes. The 

20/40/60  minute  Status  Lights  indicate  HIGH  speed 

operation. 
The  Wireless  Timers  are  to  be  surface  mounted  onto  a 

wall. Multiple Wireless Timers may be installed in a ventilation 

system.  To increase the range of a Wireless Timer, a RX02 

Repeater should be used.

Pairing:

To  pair  additional  DET02  Timers  with  the  same  wall 

control, or if  pairing  was  not  successful,  repeat steps 

1-6.
When  paired,  the  DET02  Timers  can  be  moved  and 

installed  elsewhere.    Estimated  range  of  the  Timer  is  40’ 

with no obstructions.  A RX02 Repeater may be installed to 

increase the range of the Timers.
Test if pairing was successful by pressing the Select Button 

and  listen  for  the  HRV  to  initiate  HIGH  fan  speed 

Ventilation.

Un-pairing: 

1.

Turn on the main wall control by pressing the ON/OFF

button      and remove the battery from Timer.

2.

Press the left and right buttons simultaneously on the

main wall control (     and 

   

).  The bottom  row  of

 

3

LED's  will  begin  flashing.  This  indicates  that  the

main control is now in pairing mode.

  

(Figure D)

3. Keep the Timer within 16” of the main wall control

when pairing.

4. Install the battery in the DET02 Timer.  All four lights

on the Timer will immediately flash 5 times, then only

the red battery light will remain on for approximately

12 seconds after which the "40" light flashes the rev

code. 20, 40, 60 lights will flash until paired  or will

stop if not paired within 12 seconds.  If pairing was not

successful you now must return to step 1 to restart the

pairing process.

5. Press the      button on the main wall control to exit 

pairing mode when Timers have been successfully 

paired. 

1. Remove the battery from the back of the DET02 Timer
2. Press  and  hold  the  Select  Button  on  the  front  of  the

Timer

3. While holding the Select Button, reinsert the battery in

the Timer.  Continue holding the Select Button until the

LED under "40" begins flashing.  The DET02 Timer will

now be unpaired with the main wall control.

Summary of Contents for 1500E-ECM

Page 1: ...er operating at a higher static After installation the compatibility of the two pieces of equipment must be confirmed by measuring the airflows of the Heat Recovery Ventilator HRV by using the balancing procedure found in this manual It is always important to assess how the operation of any HRV may interact with vented combustion equipment ie Gas Furnaces Oil Furnaces Wood Stoves etc NEVER install...

Page 2: ...______________________________ Submitted by ____________________________________ DEFROST Factory set defrost time Supply motor is shut off while exhaust air defrosts core WEIGHT 460 lbs 210 kg SHIPPING WEIGHT 580 lbs 260 kg NOTE All specifications are subject to change without notice DIMENSIONS 1500I ECM in inches Specifications 1500I ECM TIMER OPTIONS 99 DET01 Lifebreath 20 40 60 Minute Timer Ini...

Page 3: ...haust air defrosts core WEIGHT 530 lbs 240 kg SHIPPING WEIGHT 650 lbs 290 kg TIMER OPTIONS 99 DET01 Lifebreath 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes 3 wire connection 20 gauge wire minimum 99 DET02 Lifebreath WIRELESS 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes Wirelessly connects to main control for ease of installation 4...

Page 4: ...ir defrosts core WEIGHT 530 lbs 240 kg SHIPPING WEIGHT 650 lbs 290 kg TIMER OPTIONS 99 DET01 Lifebreath 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes 3 wire connection 20 gauge wire minimum 99 DET02 Lifebreath WIRELESS 20 40 60 Minute Timer Initiates high speed Ventilation for 20 40 or 60 minutes Wirelessly connects to main control for ease of installation 40 appro...

Page 5: ...OUTSIDE 5 The 1500E ECM E is designed for outdoor installations The duct connections for the Stale Air From Building and Fresh Air to Building ducts are at the ends of the unit The 1500E ECM is designed for outdoor rooftop installations The duct connections for the Stale Air From Building and Fresh Air to Building ducts are located at the bottom of the unit A roof curb is required for this install...

Page 6: ...ing the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After a few seconds the Dehumidistat light will either flash or be on continuous A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation A continuous light indicates the humidity level is lower than the setting Re...

Page 7: ... is measured at the control Setting the Dehumidistat Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting After 5 seconds the Dehumidistat light will either flash or be on continuous A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed ventilation A continuous light indicates the humidity level ...

Page 8: ...the middle of the screw holes Refer to Figure B or C for placement 5 Cut in a 3 4 in by 1 in oval hole in the wall to allow for the wire opening and drill two 1 8 in holes for the screws and wall anchors Figure B or C 6 Pull 3 wire 20 gauge min 100 ft length max through the opening in the wall 7 Connect red green and yellow to the Wiring Terminals located on the Back Plate Figure B or C 8 Attach t...

Page 9: ...the Back Plate Figure C 8 Attach the Back Plate to the wall using the 2 supplied screws and anchors 9 Attach the Face Plate to the Back Plate Figure B Note Be careful to correctly align the Face Plate to avoid damaging the Face Plate Contact Pins 10 Insert the Operating Instructions Card into the control Figure A 11 Connect the 3 wire 20 gauge min 100 ft length max to the digital controls terminal...

Page 10: ...essful repeat steps 1 6 When paired the DET02 Timers can be moved and installed elsewhere Estimated range of the Timer is 40 with no obstructions A RX02 Repeater may be installed to increase the range of the Timers Test if pairing was successful by pressing the Select Button and listen for the HRV to initiate HIGH fan speed Ventilation Un pairing 1 Turn on the main wall control by pressing the ON ...

Page 11: ...ess Timer When paired to the main wall control the Wireless Timer may be moved to a remote location in the home such as a bathroom Pressing the Select Button on the Timer will initiate HIGH speed fan operation The corresponding Status Light will illuminate under the number on the Timer to indicate either 20 40 or 60 minutes of HIGH speed fan operation To cancel the call for HIGH speed fan operatio...

Page 12: ... Wireless Repeater Part 99 RX02 Operating your Lifebreath 20 40 60 Minute Fan Timer Press and release the Select Button to activate a 20 40 or 60 minute high speed override cycle The High Speed Status Light will illuminate and the unit will run on high speed ventilation for the selected time The High Speed Status Light will dim after 10 seconds of run time The High Speed Status Light will flash du...

Page 13: ...ard SPEED High R W Medium R Y Low R G JUMPER 13 Optional 20 40 60 Minute Timer Part 99 DET01 Boost unit to Ventilation Mode for 20 40 60 minutes no speed change Connect up to 4 maximum Connect to Yellow Red Green HIGH OFF OFF OFF MED LOW Optional 3 Speed Control Part 99 500 Connect to R W Y and G on Thermostat T18 T5 T13 C4 T17 T19 T1 T2 T3 T4 T6 T14 T15 T16 C3 C2 C1 RELAY Fan Hi Fan Med Fan Low F...

Page 14: ...um 115V 10 amp resistive load T30 T29 T28 T43 SPARE P2 P3 F2 MAX 2 amp R 24Vac Defrost Freeze K7 K1 K2 K8 T31 T32 T33 T34 T35 T36 T37 T38 T39 T40 T41 T42 Contact 1 N 0 COM N C N 0 COM N C N 0 COM N C N 0 COM Contact 2 Contact 3 Contact 4 N C Contact 2 and 4 These relays initiate whenever the HRV fans are operating ...

Page 15: ...oth sides 2 Remove first set of filters 3 Remove filter divider panels if only accessing from one side 4 Remove filters from behind filter divider panel 5 Replace all filters Ensure that filter divider panels are re inserted into unit Servicing Cores 1 Remove core service panel one or both sides 2 Slide cores out regular core maintenance 3 When placing the cores back into the unit ensure that ther...

Page 16: ...16 Option 1 Unit can be suspended with U channels and Threaded Rod Option 2 Mounting the 1500 Unit can be placed on blocks sleepers ...

Page 17: ...s under deck Securing the Frame To ensure proper mating with unit it is critical that mounting frame be squared to the roof as follows 1 With frame situated level in desired location on roof trusses tack weld one corner of frame 2 Measure frame diagonally from one corner to the opposite corner Repeat with the remaining two corners These dimensions must be equal for the frame to be square 3 It is e...

Page 18: ...LY TOP VIEW SIDE VIEW 14 356 mm 16 406 mm 19 483 mm 65 3 4 1670 mm 1 3 4 45 mm 1 3 4 45 mm 42 3 4 1086 mm 16 406 mm 19 483 mm 1 3 4 45 mm 1 3 4 45 mm STALE AIR RETURN FRESH AIR SUPPLY DUCT COLLAR SUPPORTS FACTORY INSTALLED PERIMETER WOODEN NAILER STRIP ...

Page 19: ...to be built elsewhere and provided by the contractor NOTE It is extremely important to design and install the fresh air intake in an area where the hoods will gather the freshest air free from restriction Recommended no less than 10 ft 3 m apart from each other at least 18 in 46 cm above ground level away from sources of contaminants such as automobile exhaust fumes gas meters garbage containers c...

Page 20: ...y isolated and separately grounded electrically from the air handler This will avoid a possible shock hazard to service people if a short to ground develops in one of the devices It may be necessary to install a separate fresh air supply ductwork system if the heating is other than forced air When installing an HRV the designer and installer should be aware of local codes that may require smoke de...

Page 21: ...ed directly into the ceiling space but this should occur near the air handler s intake By operating the HRV ERV on a 24 hour 7 day battery backed timer the unit can be set to operate only when occupancy or indoor conditions require the air exchange In installations where it is satisfactory to provide general exhaust from the space the air to be exhausted may be taken directly from the return air p...

Page 22: ...FWDEOH VSHHGV LJK PHGLXP DQG ORZ DFK RI WKHVH VSHHGV FDQ EH IXUWKHU DGMXVWHG WR REWDLQ WKH GHVLUHG DLUIORZ 7KLV LV GRQH RQ WKH 0 FLUFXLW ERDUG ORFDWHG ZLWKLQ WKH HOHFWULFDO ER RWK PRWRUV FRQWDLQ D VHSDUDWH 0 FLUFXLW ERDUG WR DOORZ IRU LQGHSHQGHQW DGMXVWPHQW RI WKH PRWRUV 7KH DGMXVW WDS ZLOO FKDQJH WKH DLUIORZV RQ DOO WKUHH RI WKH VSHHGV 3OHDVH QRWH WKDW WKLV XQLW KDV EHHQ IDFWRU VHW WR REWDLQ 0 DW...

Page 23: ...e unit Drill a small hole in the duct about 3 16 three feet downstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a manometer capable of reading 3 digits of resolution The tube coming out of the top of the pitot is connected to the high pr...

Page 24: ...24 Wiring Diagram Neutral Neutre CHASSIS T44 Line Ligne C3 C2 C1 ...

Page 25: ...ndon Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labor required to install any replacement part s shall be dealt with at the option of the customer in either of the following ways a the customer may supply labor at their own expense or b if the product was purchased from a dealer then the dealer will supply labor at co...

Page 26: ...26 ...

Page 27: ...27 ...

Page 28: ...info lifebreath com T 1 855 247 4200 F 1 800 494 4185 69 1500 110116 ...

Reviews: