20 Wiring Inspection
Table 3
Table 310-16
Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F)
1
Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30° (86°F)
Size
Temperature Rating of Conductor. See Table 310-13.
Size
AWG
kcmil
60°C
(140°F)
75°C
(167°F)
90°C
(194°F)
60°C
(140°F)
75°C
(167°F)
90°C
(194°F)
AWG
kcmil
Types
TW†
UF†
Types
FEPW+,
RH,RHW†,
THHW†,
THW†,
THWN†,
XHHW†,
USE†, ZW†
Types
TBS, SA,
SIS,FEP†,
FEPB†,MI,
RHH†, RHW-2
THHN†,THHW†,
THW-2,THWN-2,
USE-2, XHH,
XHHW†
XHHW-2,ZW-2
Types
TW†
UF†
Types
RH†, RHW†,
THHW†,
THW†,
THWN†,
XHHW†,
USE†
Types
TBS,
SA,SIS,
THHN†,
THHW†,
THW-2, THWN-2,
RHH†, RHW-2,
USE-2,
XHH, XHHW†,
XHHW-2, ZW-2
Copper
Aluminum or Copper-Clad Aluminum
18
16
14
12
10
8
.......
.......
20†
25†
30
40
.......
.......
20†
25†
35†
50
14
18
25†
30†
40†
55
.......
.......
.......
20†
25
30
.......
.......
.......
20†
30†
40
.......
.......
.......
25†
35†
45
.......
.......
.......
12
10
8
6
4
3
2
1
55
70
85
95
110
65
85
100
115
130
75
95
110
130
150
40
55
65
75
85
50
65
75
90
100
60
75
85
100
115
6
4
3
2
1
1/0
2/0
3/0
4/0
125
145
165
195
150
175
200
230
170
195
225
260
100
115
130
150
120
135
155
180
135
150
175
205
1/0
2/0
3/0
4/0
250
300
350
400
500
215
240
260
280
320
255
285
310
335
380
290
320
350
380
430
170
190
210
225
260
205
230
250
270
310
230
255
280
305
350
250
300
350
400
500
600
700
750
800
900
355
385
400
410
435
420
460
475
490
520
475
520
535
555
585
285
310
320
330
355
340
375
385
395
425
385
420
435
450
480
600
700
750
800
900
1000
1250
1500
1750
2000
455
495
520
545
560
545
590
625
650
665
615
665
705
735
750
375
405
435
455
470
445
485
520
545
560
500
545
585
615
630
1000
1250
1500
1750
2000
Correction Factors
Ambient
Temp °C
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown
above by the appropriate factor shown below.
Ambient
Temp °F
21-25
26-30
31-35
36-40
41-45
46-50
51-55
56-60
61-70
71-80
1.08
1.00
.91
.82
.71
.58
.41
.......
.......
.......
1.05
1.00
.94
.88
.82
.75
.67
.58
.33
.......
1.04
1.00
.96
.91
.87
.82
.76
.71
.58
.41
1.08
1.00
.91
.82
.71
.58
.41
.......
.......
.......
1.05
1.00
.94
.88
.82
.75
.67
.58
.33
.......
1.04
1.00
.96
.91
.87
.82
.76
.71
.58
.41
70-77
78-86
87-95
96-104
105-113
114-122
123-131
132-140
141-158
159-176
† Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an
obelisk (†) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for
No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and
number of conductors have been applied.
1
Reprinted with permission from NFPA 70-1993, the National Electrical Code®, Copyright 1996, National Fire Protection Association,
Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association, on the
referenced subject which is represented only by the standard in its entirety.
Summary of Contents for Series 600
Page 2: ......
Page 6: ...iv ...
Page 15: ...Inspections 9 Figure 3 System Control Cabinets ...
Page 21: ...Wiring Considerations 15 Figure 4 Typical Multi Module Configurations ...
Page 22: ...16 Wiring Considerations Figure 4 Typical Multi Module Configurations continued ...
Page 27: ...Wiring Inspection 21 Figure 5 Outline Drawing 338 kVA ...
Page 28: ...22 Wiring Inspection Figure 6 Outline Drawing 400 kVA ...
Page 29: ...Wiring Inspection 23 Figure 7 Outline Drawing 500 kVA ...
Page 30: ...24 Wiring Inspection Figure 8 Outline Drawing 500 kVA 208 VAC ...
Page 31: ...Wiring Inspection 25 Figure 9 Outline Drawing 625 kVA ...
Page 32: ...26 Wiring Inspection Figure 10 Outline Drawing 750 kVA High Link 240 Cells ...
Page 33: ...Wiring Inspection 27 Figure 11 Outline Drawing 750 kVA Low Link 180 Cells ...
Page 34: ...28 Wiring Inspection Figure 12 Outline Drawing 1000 kVA ...
Page 35: ...Wiring Inspection 29 Figure 13 Outline Drawing System Control Cabinet SCCB 640 to 800 Amps ...
Page 36: ...30 Wiring Inspection Figure 14 Outline Drawing System Control Cabinet SCCB 1280 to 1600 Amps ...
Page 37: ...Wiring Inspection 31 Figure 15 Outline Drawing System Control Cabinet SCCB 2000 to 3000 Amps ...
Page 38: ...32 Wiring Inspection Figure 16 Outline Drawing System Control Cabinet SCCB 4000 Amps ...
Page 39: ...Wiring Inspection 33 Figure 17 Outline Drawing System Control Cabinet SCCP 200 to 480 Amps ...
Page 40: ...34 Wiring Inspection Figure 18 Outline Drawing System Control Cabinet SCCP 560 to 960 Amps ...
Page 41: ...Wiring Inspection 35 Figure 19 Outline Drawing System Control Cabinet SCCP 1280 to 2000 Amps ...
Page 42: ...36 Wiring Inspection Figure 20 Outline Drawing System Control Cabinet SCCA 2000 to 4000 Amps ...
Page 43: ...Wiring Inspection 37 Figure 21 Base Mounting Details 338 kVA ...
Page 44: ...38 Wiring Inspection Figure 22 Base Mounting Details 400 and 500 kVA ...
Page 47: ...Wiring Inspection 41 Figure 25 Base Mounting Details 625 kVA and 750 kVA High Link 240 Cells ...
Page 51: ...Wiring Inspection 45 Figure 29 Base Mounting Patterns System Control Cabinets SCCB 4000 Amps ...
Page 55: ...Wiring Inspection 49 Figure 33 Shipping Split Detail 338 kVA ...
Page 56: ...50 Wiring Inspection Figure 34 Shipping Split Detail 400 and 500 kVA ...
Page 57: ...Wiring Inspection 51 Figure 35 Shipping Split Detail 400 and 500 kVA 208 VAC ...
Page 58: ...52 Wiring Inspection Figure 36 Shipping Split Detail 625 kVA ...
Page 59: ...Wiring Inspection 53 Figure 37 Shipping Split Detail 750 kVA High Link 240 Cells ...
Page 60: ...54 Wiring Inspection Figure 38 Shipping Split Detail 750 kVA Low Link 180 Cells and 1000 kVA ...
Page 61: ...Wiring Inspection 55 Figure 39 Optional Shipping Split Detail 400 to 625 kVA ...
Page 62: ...56 Wiring Inspection Figure 40 Optional Shipping Split Detail 750 kVA ...
Page 64: ...58 Wiring Inspection Figure 42 Bussing Details 338 kVA ...
Page 65: ...Wiring Inspection 59 Figure 43 Bussing Details 400 kVA ...
Page 66: ...60 Wiring Inspection Figure 44 Bussing Details 500 kVA ...
Page 67: ...Wiring Inspection 61 Figure 45 Bussing Details 500 kVA 208 VAC ...
Page 68: ...62 Wiring Inspection Figure 46 Bussing Details 625 kVA ...
Page 69: ...Wiring Inspection 63 Figure 47 Bussing Details 750 kVA High Link 240 Cells ...
Page 70: ...64 Wiring Inspection Figure 48 Bussing Details 750 kVA Low Link 180 Cells ...
Page 71: ...Wiring Inspection 65 Figure 49 Bussing Details 1000 kVA ...
Page 72: ...66 Wiring Inspection Figure 50 Module One Line Diagram 338 kVA ...
Page 73: ...Wiring Inspection 67 Figure 51 Module One Line Diagram 400 kVA ...
Page 74: ...68 Wiring Inspection Figure 52 Module One Line Diagram 500 kVA ...
Page 75: ...Wiring Inspection 69 Figure 53 Module One Line Diagram 500 kVA 208 VAC ...
Page 76: ...70 Wiring Inspection Figure 54 Module One Line Diagram 625 kVA ...
Page 77: ...Wiring Inspection 71 Figure 55 Module One Line Diagram 750 kVA High Link 240 Cells ...
Page 78: ...72 Wiring Inspection Figure 56 Module One Line Diagram 750 kVA Low Link 180 Cells ...
Page 79: ...Wiring Inspection 73 Figure 57 Module One Line Diagram 1000 kVA ...
Page 80: ...74 Wiring Inspection Figure 58 One Line Diagram System Control Cabinet SCCA ...
Page 83: ...Wiring Inspection 77 Figure 61 Control Wiring Interconnect Diagram ...
Page 84: ...78 Wiring Inspection Figure 62 Control Wiring Interconnect Diagram SCCA and Switchgear ...
Page 85: ...Wiring Inspection 79 Figure 63 Control Connection Location Diagram Module ...
Page 86: ...80 Wiring Inspection Figure 64 Control Connection Location Diagram System Control Cabinet ...
Page 87: ...Wiring Inspection 81 Figure 65 Video Display Terminal Wiring ...
Page 88: ...82 Wiring Inspection Figure 66 Battery Circuit Breaker ...
Page 89: ...Wiring Inspection 83 Figure 67 Parallel Battery Configurations ...
Page 90: ...84 Wiring Inspection Figure 68 Remote Status Panel ...