PowerSure PSA

Guide Specification

350 – 1000VA

SL-23271 8/03

4

F.

 

Voltage Transient Response:

 ±15% in Normal mode for 0-100-0% loading of the UPS

rating, ±5% in Battery mode for 20-100-20% loading of the UPS rating.

G. 

 

Transient Recovery Time: 

To within ±8% of nominal voltage in < 2 cycles.

H. 

 

Efficiency:

 >95% (Normal mode)

 >90% (Buck/Boost mode)

I. 

Output Power Cords:

 The 230 VAC units have two (2) detachable IEC-320-C14 output 

power cords measuring 2m (6.6 ft) in length.

1.4

ENVIRONMENTAL CONDITIONS

A. Ambient Temperature

Operating:

 32

o

 104

o

F (0

o

 40

o

C) for altitudes 0 

 5,000 ft. (0 

 1500 meters) above sea

level

 32°F 

 86°F (0°C 

 30°C) for altitudes 5000 ft 

 10,000 ft (1500 

 3000 meters)

above sea level.

77

o

 F (25

o

C) for optimum battery performance

Storage: 

5°F 

 104°F (-15°C 

 40°C) with batteries

 5

o

 122

o

F (

-

15

o

 50

o

C) without batteries

 68

o

F (20

o

C) for optimum battery storage.

B. Relative Humidity

 95% non-condensing.

C. Altitude

:

3,000 m (10,000 ft. max.), without power derating when operated within the temperature specified
in section 1.4.A.

D. Audible Noise

Noise generated by the UPS during normal operation does not exceed 40dB when measured at 1
meter from the surface of the UPS, “A” weighted.

E. Electrostatic Discharge

The 120 VAC units are able to withstand an electrostatic discharge compliant to EN61000-4-2,
level 3, Criteria A without damage and without affecting the connected load. The 230 VAC units
are able to withstand an electrostatic discharge compliant to EN61000-4-2, level 3, Criteria A
without damage and without affecting the connected load.

1.5

USER ACCESSORIES AND PACKAGING 

The specified UPS system is supplied with one (1) user's manual. The manual includes installation
drawings and instructions, a functional description of the equipment, safety precautions, illustrations,
operating procedures, and general maintenance guidelines.  The UPS is also supplied with one (1)
Multilink

 software CD, one (1) Multilink serial cable (10-ft; 3m), one (1) USB cable (6-ft; 1.8m), one (1)

RJ-11 cord (7-ft; 2.1m) and one (1) warranty card (120V models only).  The package of the 230 VAC units
also includes two (2) output power cords (2m; 6.6 ft).  The package meets the requirements of ISTA
Procedure 1A.

1.6

WARRANTY

The manufacturer warrants the UPS against defects in materials and workmanship for two (2) years.  The
warranty covers all parts.  An optional one (1) or three (3) year extended warranty is available from the
manufacturer.

Summary of Contents for PowerSure PSA 350VA to 1000VA

Page 1: ...herein the statements in this specification will govern 120V Units UL 1778 c UL listed to CSA 22 2 No 107 1 FCC Part 15 Subpart B Class B ANSI C62 41 Category A Level 3 IEEE 587 Category A EN61000 4 5 Level 3 Criteria A EN61000 4 2 Level 3 Criteria A EN61000 4 3 Level 3 Criteria A EN61000 4 4 Level 4 Criteria A EN61000 4 6 Level 3 Criteria A EN61000 3 2 EN61000 3 3 ISTA Procedure 1A 230V Units EN5...

Page 2: ... specifications of the UPS are Input 120V Units 0 160 VAC 60 50 Hz auto sensing single phase 2 wire plus ground 230V Units 0 300 VAC 50 60 Hz auto sensing single phase 2 wire plus earth Output 120V Units 110 120 127 VAC 10 60 50 Hz single phase 2 wire plus ground DIP Switch selectable 230V Units 220 230 240 VAC 10 50 60 Hz single phase 2 wire plus earth DIP Switch selectable B Output Load Capacity...

Page 3: ...its can withstand input surges of up to 570J without damage per criteria listed in IEEE C62 41 Category A Level 3 The 230 VAC units can withstand input surges of up to 660J without damage per criteria listed in EN61000 4 5 Level 3 Criteria A D Input Connections The 120 VAC units have an attached input cord 6 0 feet 1 8 meters in length measured between the inside edges of the connectors The attach...

Page 4: ...xceed 40dB when measured at 1 meter from the surface of the UPS A weighted E Electrostatic Discharge The 120 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and without affecting the connected load The 230 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and wi...

Page 5: ...e UPS cabinet is injection molded standard color Dimensions and weights are UNIT UNIT DIMENSIONS W x D x H in mm 120 VAC UNITS WEIGHT lbs kg 230 VAC UNITS WEIGHT kg lbs 350VA 4 6 x 7 7 x 8 7 116 x 196 x 222 16 8 7 6 7 15 4 500VA 4 6 x 7 7 x 8 7 116 x 196 x 222 17 2 7 8 7 4 16 3 650VA 4 6 x 14 1 x 8 7 116 x 358 x 222 20 7 9 4 9 1 20 1 1000VA 4 6 x 14 1 x 8 7 116 x 358 x 222 29 7 13 5 13 2 19 1 2 1 ...

Page 6: ... 2 2 3 Bi Directional Converter DC Protection The following DC shutdown levels protect the UPS DC Overvoltage Shutdown DC Undervoltage Shutdown End of Discharge DC Undervoltage Warning Low Battery Reserve 2 2 2 4 Output Protection For output faults including short circuits and overloads the UPS is protected by the input circuit protector during Normal mode and by electronic current limiting during...

Page 7: ... than 0 5 sec will start up the UPS and to turn the UPS off the button will need to be depressed for more than 2 sec 2 2 3 4 On Line Battery Test The UPS is provided with an automatic biweekly battery test feature The test ensures the capability of the battery to supply power to the inverter while loaded If the battery fails the test the UPS will display a warning to indicate the batteries need re...

Page 8: ...on settings This shutdown signal 5 12VDC must have a duration of at least 1 5 seconds for the UPS to be shut down The UPS communicates via serial communications using Liebert ESP II protocol The PowerSure PSA has a USB interface port for communication that will work with the built in Microsoft Power Manager software on the user s PC if the PC is so equipped It will provide UPS status and manages t...

Reviews: