Liebert PowerSure PSA 350VA to 1000VA Specifications Download Page 2

PowerSure PSA

Guide Specification

350 – 1000VA

SL-23271 8/03

2

B. Voltage Boost/Buck -

 During input power source abnormalities (sags and swells), the AC

output power is corrected by means of boost (sag correction) or buck (swell correction)
compensation taps.  Operation of the compensation taps automatically maintains the proper
output voltage for the connected critical equipment.  The compensation taps is designed for
indefinite operation to their limits. Operation of the compensation taps will not discharge the
battery.

C. Recharge -

 Upon restoration of utility / mains AC power, after a utility / mains AC power

outage and complete or partial battery discharge, the unit automatically restarts and resumes
supplying power to the critical AC load; and the battery charger recharges the battery.

D.

 

Battery - 

When the input power source exceeds the parameters defined in section 1.3.3.1, the

critical AC load is supplied power by the inverter, which obtains its power from the battery.
Typical detection and transfer time is 4-6 ms.

E. Battery Start- 

The UPS is capable of starting without input power.  The unit starts up and

operates from the battery, with output frequency the same as the last operating frequency.

1.3.2

Design Requirements

A. Voltage

:  Input/output voltage specifications of the UPS are:

Input: 

120V Units:  0-160 VAC, 60/50 Hz auto-sensing, single-phase, 2-wire-plus-ground.
230V Units:  0-300 VAC, 50/60 Hz auto-sensing, single-phase, 2-wire-plus-earth.

Output: 

120V Units:  110/120/127 VAC ±10%, 60/50 Hz, single-phase, 2-wire-plus-ground.
(DIP Switch selectable)
230V Units:  220/230/240 VAC ±10%, 50/60 Hz, single-phase, 2-wire-plus-earth.
(DIP Switch selectable)

B. Output Load Capacity:

 Maximum specified output load capacity of the UPS, regardless of

load power factor, is:

350VA / 210W

500VA / 300W

650VA / 390W

1000VA / 600W

C. Internal Battery

: The battery consists of valve regulated, non-spillable, maintenance-free,

sealed, lead-acid cells.  The battery is user replaceable and hot swappable.  

D. Battery Reserve Time:

 5 minutes typical at full load with ambient temperature 77

°

F (25

°

C).

E. Battery Recharge:

 The UPS contains a battery recharge rate designed to prolong battery life.

Recharge time is 6 hours typical to 90% capacity after a complete discharge into full resistive
load.

1.3.3

Performance Requirements

1.3.3.1 AC Input to UPS

A. 

 

Voltage Configuration:

 The UPS operates at these values without drawing power from the

batteries.

110 VAC nominal: single phase, 2-wire-plus-ground: 78 

 138 VAC (±3VAC), 

Buck compensation: 122VAC (±3VAC)
Boost1 compensation: 98VAC (±3VAC)
Boost2 compensation: 87VAC (±3VAC)

120 VAC nominal: single phase, 2-wire-plus-ground: 85 

 145 VAC (±3VAC), 

Buck compensation: 133VAC (±3VAC)
Boost1 compensation: 107VAC (±3VAC)
Boost2 compensation: 95VAC (±3VAC)

Summary of Contents for PowerSure PSA 350VA to 1000VA

Page 1: ...herein the statements in this specification will govern 120V Units UL 1778 c UL listed to CSA 22 2 No 107 1 FCC Part 15 Subpart B Class B ANSI C62 41 Category A Level 3 IEEE 587 Category A EN61000 4 5 Level 3 Criteria A EN61000 4 2 Level 3 Criteria A EN61000 4 3 Level 3 Criteria A EN61000 4 4 Level 4 Criteria A EN61000 4 6 Level 3 Criteria A EN61000 3 2 EN61000 3 3 ISTA Procedure 1A 230V Units EN5...

Page 2: ... specifications of the UPS are Input 120V Units 0 160 VAC 60 50 Hz auto sensing single phase 2 wire plus ground 230V Units 0 300 VAC 50 60 Hz auto sensing single phase 2 wire plus earth Output 120V Units 110 120 127 VAC 10 60 50 Hz single phase 2 wire plus ground DIP Switch selectable 230V Units 220 230 240 VAC 10 50 60 Hz single phase 2 wire plus earth DIP Switch selectable B Output Load Capacity...

Page 3: ...its can withstand input surges of up to 570J without damage per criteria listed in IEEE C62 41 Category A Level 3 The 230 VAC units can withstand input surges of up to 660J without damage per criteria listed in EN61000 4 5 Level 3 Criteria A D Input Connections The 120 VAC units have an attached input cord 6 0 feet 1 8 meters in length measured between the inside edges of the connectors The attach...

Page 4: ...xceed 40dB when measured at 1 meter from the surface of the UPS A weighted E Electrostatic Discharge The 120 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and without affecting the connected load The 230 VAC units are able to withstand an electrostatic discharge compliant to EN61000 4 2 level 3 Criteria A without damage and wi...

Page 5: ...e UPS cabinet is injection molded standard color Dimensions and weights are UNIT UNIT DIMENSIONS W x D x H in mm 120 VAC UNITS WEIGHT lbs kg 230 VAC UNITS WEIGHT kg lbs 350VA 4 6 x 7 7 x 8 7 116 x 196 x 222 16 8 7 6 7 15 4 500VA 4 6 x 7 7 x 8 7 116 x 196 x 222 17 2 7 8 7 4 16 3 650VA 4 6 x 14 1 x 8 7 116 x 358 x 222 20 7 9 4 9 1 20 1 1000VA 4 6 x 14 1 x 8 7 116 x 358 x 222 29 7 13 5 13 2 19 1 2 1 ...

Page 6: ... 2 2 3 Bi Directional Converter DC Protection The following DC shutdown levels protect the UPS DC Overvoltage Shutdown DC Undervoltage Shutdown End of Discharge DC Undervoltage Warning Low Battery Reserve 2 2 2 4 Output Protection For output faults including short circuits and overloads the UPS is protected by the input circuit protector during Normal mode and by electronic current limiting during...

Page 7: ... than 0 5 sec will start up the UPS and to turn the UPS off the button will need to be depressed for more than 2 sec 2 2 3 4 On Line Battery Test The UPS is provided with an automatic biweekly battery test feature The test ensures the capability of the battery to supply power to the inverter while loaded If the battery fails the test the UPS will display a warning to indicate the batteries need re...

Page 8: ...on settings This shutdown signal 5 12VDC must have a duration of at least 1 5 seconds for the UPS to be shut down The UPS communicates via serial communications using Liebert ESP II protocol The PowerSure PSA has a USB interface port for communication that will work with the built in Microsoft Power Manager software on the user s PC if the PC is so equipped It will provide UPS status and manages t...

Reviews: