Specifications
35
12.0 S
PECIFICATIONS
Table 7
UPS specifications
Model #
GXT3-5000RT230
GXT3-6000RT230
GXT3-10000RT230
Rating
5000VA/4000W
6000VA/4800W
10000VA/9000W
Dimensions, mm (in)
Unit, W x D x H
430 x 574 x 217 (16.9 x 22.4 x 8.5)
430 x 581 x 261 (16.9 x 22.9 x 10.3)
Shipping, W x D x H
516 x 745 x 530 (20.3 x 29.3 x 20.9)
530 x 745 x 563 (20.9 x 29.3 x 22.2)
Weight, kg (lb)
Unit
60 (132.2)
70 (154.3)
Shipping
71 (156.5)
92 (202.8)
Input AC Parameters
Operating Frequency, Nom
50 or 60Hz (Factory Default = 50)
Factory Default VAC
230VAC
User-Configurable VAC
220/230/240VAC
(May be modified using included configuration program)
Operating Voltage Range
Without Battery Operation
176 - 280VAC
Maximum Allowable VAC
280VAC
Input Frequency Without
Battery Operation
40 - 70Hz
Input Power Connection
PD2-CE6HDWRMBS Standard
(See
3.3 - Removable Power Distribution Box
)
PD2-CE10HDWRMBS Standard
(See
3.3 - Removable Power
Distribution Box
)
Output AC Parameters
AC-AC efficiency
92% AC-AC
Factory Default VAC
230VAC
Output Connections
PD2-CE6HDWRMBS Standard
(See
3.3 - Removable Power Distribution Box
)
PD2-CE10HDWRMBS Standard
(See
3.3 - Removable Power
Distribution Box
)
Frequency
50Hz or 60Hz, Nominal
Waveform
Sinewave
Main Mode Overload
>200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1 minute
Internal Battery Charger
Charger Current
1.3
2.6
Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
Quantity x V
20 x 12V
Battery Mfr. / Part #
5AH battery, CSB HR1221W or YUASA NPH5-12
9AH battery, CSB HR1234W
or Panasonic UP-RW1245
Backup Time
See
Table 11 - Battery run time, minutes, all models
Recharge Time (Internal
Batteries)
3 hr. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass Operation
If input voltage exceeds ±15% of the nominal voltage
Re-Enable Bypass
Operation
If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation
When the input frequency prevents synchronous operation
Environmental
Operating Temperature,
°C (°F)
0 to 40 (32 to 104) see
Table 8 - Operating temperature parameters
Storage Temperature,
°C (°F)
-15 to 50 (5 to 122)
Summary of Contents for GXT3-10000RT230
Page 1: ...AC Power For Business Critical Continuity Liebert GXT3 230V 5000 10 000VA User Manual...
Page 2: ......
Page 6: ...iv...
Page 46: ...Specifications 40...
Page 47: ......