background image

Maintenance

31

10.4

Checking UPS Status

Emerson recommends checking the UPS operation status every six months.

• Check whether the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an alarm?
• Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal 

Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or 

Emerson Channel Support.

• Check whether the battery is discharging. When the mains input is normal, the battery should 

not discharge. If the UPS is operating in Battery Mode, stop and contact your local Emerson rep-

resentative or Emerson Channel Support.

10.5

Checking UPS Functions

Emerson recommends checking the UPS functions once every six months.
Back up the load data before conducting the UPS functions check. Procedures are as follows:
1. Press the Standby/Manual Bypass button to check whether the buzzer and indicators are normal.
2. Press the On/Alarm Silence/Manual Battery Test button to check again whether the indicators 

are on and the UPS is operating normally. 

3. Press the On/Alarm Silence/Manual Battery Test button for three seconds after Inverter Mode. 

The UPS should initiate a battery self-test. Check to determine whether the battery is operating 

normally. If not, stop and contact your local Emerson representative or Emerson Channel Support

NOTE

UPS function check procedures may interrupt power supply to the connected load.

Summary of Contents for GXT3-10000RT230

Page 1: ...AC Power For Business Critical Continuity Liebert GXT3 230V 5000 10 000VA User Manual...

Page 2: ......

Page 3: ...11 5 1 1 Tower UPS Installation 11 5 1 2 Rack Mount UPS Installation 12 5 1 3 Installing the Adjustable Rack Mount Kit Sold Separately 12 5 2 External Battery Cabinet Installation 14 5 3 Connect Inpu...

Page 4: ...ry 27 9 2 4 Low Battery 27 9 3 Liebert IntelliSlot Communication Cards 27 9 3 1 Liebert MultiLink 28 9 4 Remote Emergency Power Off 28 10 0 MAINTENANCE 29 10 1 Replacing the Internal Battery Pack 29 1...

Page 5: ...2 CE10HDWRMBS 18 Figure 13 Load level indicators 21 Figure 14 Battery level indicators 22 Figure 15 Remove cover from IT Power System Connectors compartment 25 Figure 16 Terminal block communication t...

Page 6: ...iv...

Page 7: ...this manual NOTICE If this UPS is supplied from an IT electrical power system the jumper on the rear panel must be disconnected See 8 8 IT Power System Configuration for details If connecting to an IT...

Page 8: ...e of batteries and the required precautions Keep unauthorized personnel away from the batteries Proper disposal of batteries is required Refer to your local laws and regulations for disposal requireme...

Page 9: ...tant instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to...

Page 10: ...at continuously conditions and regulates its output voltage whether mains power is present or not It supplies connected equipment with clean sinewave power Sensitive electronic equipment operates best...

Page 11: ...UPS The amount of distortion reflected on the mains is reduced This results in cleaner power being available to other devices in the building not being protected by the Liebert GXT3 2 3 Inverter In no...

Page 12: ...o extend battery run times For run times see Table 11 2 7 Dynamic Bypass The Liebert GXT3 provides an alternate path for mains power to the connected load in the unlikely event of a UPS malfunction Sh...

Page 13: ...in Frame and Electronics The cabinet is shipped with internal batteries installed and a basic hardwire distribution box attached and ready to install Figure 1 Liebert GXT3 5000VA and 6000VA front view...

Page 14: ...ower Distribution Box factory attached in bottom left corner C13 Output Receptacles C19 Output Receptacles Liebert IntelliSlot Port USB Port Terminal Block Communication Knockouts for Hardwired Power...

Page 15: ...5 Power distribution box for GXT3 10 000VA model NOTE Hardwire and hardwire receptacle boxes that include a manual bypass switch allow AC power to continue to flow from the mains input to the load whi...

Page 16: ...ual electronic version USB cable one 2m 6 1 2 ft long Mounting hardware including screws and handles Power Distribution Box installed on Liebert GXT3 Support base set one Warnings Safety Instructions...

Page 17: ...lable space and use considerations Determine the type of installation and follow the appropriate instructions in either 5 1 1 Tower UPS Installation or 5 1 2 Rack Mount UPS Installation 5 1 1 Tower UP...

Page 18: ...ount Kit you will use the following instructions The figures accompanying 5 1 3 Installing the Adjustable Rack Mount Kit Sold Separately shows the positioning of the rack mounting brackets Liebert rec...

Page 19: ...r 4 rack mounting rails 4 Get eight 8 M4 screws and eight 8 M4 nuts from the hardware pack in this kit Each nut has a locking nylon insert that begins gripping the screw when it is halfway tight Make...

Page 20: ...securing holes are provided on the front of the equipment that align with the center holes on the return flange of the front members you can use the four 4 extra M5 screws provided in the kit to secur...

Page 21: ...it about 2 seconds 6 Verify the External Battery Cabinet breaker is in the Off position 7 Connect the supplied external battery cabinet cable to the rear of the external battery cabinet then to the r...

Page 22: ...ox releases 6 Remove the power distribution box from the UPS and set it aside 7 Loosen screws over the plastic cover for the connector on the rear of the panel 8 Slide plastic cover over connector and...

Page 23: ...does not disconnect power from the manual bypass breaker Figure 11 Distribution box electrical connections diagram Terminal Block Connections PD2 CE6HDWRMBS and PD2 CE10HDWRMBS Conduit entry holes are...

Page 24: ...nect should be within sight of the UPS or have an appropriate lock out Maintain service space around the UPS or use flexible conduit The installer must provide output distribution panels circuit break...

Page 25: ...Restart Select frequency converter operation with a fixed output frequency of 50 or 60 Hz Set the Low Battery Warning alarm time from 2 to 30 minutes Enable Disable the Auto Battery test Set the Auto...

Page 26: ...for 24 hours After 24 hours retest the batteries After the batteries have been retested if only three of the five Battery LEDs illuminate contact your local dealer Emerson representative or Emerson C...

Page 27: ...ate and flash to indicate the battery capacity level The Liebert GXT3 battery capacity level is shown in 20 increments 5 The battery level indicators will illuminate as shown in Figure 14 The battery...

Page 28: ...mal Off during mains failure Battery Indicator Amber On when the battery is supplying power Off when the battery is not supplying power Inverter Indicator Green On when the inverter is supplying power...

Page 29: ...y the expected L1 N voltage Verify that the same voltages appear at the Output terminals The Bypass lamp by the switch will light 8 After verifying proper input voltage to the UPS terminal block turn...

Page 30: ...rs are illuminated refer to 11 0 Troubleshooting 8 5 Shut Down the Liebert GXT3 1 Transfer the UPS to manual bypass by pressing the Standby Manual Bypass button and holding it for about 2 seconds If m...

Page 31: ...on the IT Power System Access Cover as shown in Figure 15 2 Disconnect the connectors as shown in figure 3 Install IT Power System Access Cover and screws Figure 15 Remove cover from IT Power System C...

Page 32: ...y Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location Activation of the Any Mode Shutdown will be logged as an event in the event history log...

Page 33: ...ert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and del...

Page 34: ...on four computers and coordinate shutdown in the event of a power failure The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers support for...

Page 35: ...sen and remove the six screws on the battery door as shown in Figure 17 3 Lay the battery door and screws aside for reassembly Figure 17 Removing the front plastic bezel cover and battery door 4 Gentl...

Page 36: ...for a long time Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries 10 3 Precautions Although the Liebert GXT3...

Page 37: ...son Channel Support 10 5 Checking UPS Functions Emerson recommends checking the UPS functions once every six months Back up the load data before conducting the UPS functions check Procedures are as fo...

Page 38: ...4 Indicator descriptions Indicator Diagnosis Audible alarm A E On bypass from output overload half second beep every half second A On bypass due to overtemperature condition 1 second beep every 4 seco...

Page 39: ...PS is operating from battery mode Save data and close applications Replace UPS input fuse then restart UPS Mains power is out of tolerance UPS is operating from battery mode Save data and close applic...

Page 40: ...tative or Emerson Channel Support Fault indicator and diagnostic A and B indicators are illuminated UPS failure includes dual fan failure single fan failure under certain conditions and battery charge...

Page 41: ...y 92 AC AC Factory Default VAC 230VAC Output Connections PD2 CE6HDWRMBS Standard See 3 3 Removable Power Distribution Box PD2 CE10HDWRMBS Standard See 3 3 Removable Power Distribution Box Frequency 50...

Page 42: ...ble 8 Operating temperature parameters Ambient Temperature C F pf 30 C 3 C pf 86 F 5 4 F pf 40 C 3 C pf 104 F 5 4 F 5000RT230 6000RT230 0 8pf 0 8pf 10000RT230 0 9pf 0 8pf Table 9 Power distribution sp...

Page 43: ...475 20 9 x 29 3 x 18 7 Weight kg lb Unit 43 94 8 65 143 3 Shipping 54 119 76 167 6 Battery Parameters Type Valve regulated non spillable lead acid Quantity x V 1 x 20 x 12V Battery Manufacturer Part C...

Page 44: ...External Battery Cabinet 10 187 158 149 20 106 97 82 30 78 65 50 40 53 48 39 50 47 40 28 60 40 33 22 70 34 26 17 80 28 22 15 90 23 19 13 100 21 17 11 Internal Battery 2 External Battery Cabinets 10 21...

Page 45: ...ed run time calculation only under certain conditions The UPS must have a steady load that is greater than 20 The UPS must be at 100 charge at the start of a battery discharge The battery discharge mu...

Page 46: ...Specifications 40...