26 Equipment Inspection and Start-Up
Table 5
Torque Specifications (Unless Otherwise Labeled)
A. Nut and Bolt Combinations
Bolt
Shaft Size
Grade 2
Standard
Electrical Connections
with Belleville Washers
lb-in
N-m
lb-in
N-m
1/4
53
6.0
46
5.2
5/16
107
12.1
60
6.8
3/8
192
21.7
95
10.7
1/2
528
60.0
256
28.9
B. Main Input and Main Output Circuit Breakers
Breaker Size
Wire
Size
Compression Lug
lb-in
N-m
Up to 110 Amp
#14 - #10
#8 - #3
#2 - #3/0
35
100
150
4.0
11.4
17.1
125 to 250 Amp
#3 - #1
#1/0 - 350 kcmil
200
275
22.8
31.3
300 to 800 Amp
#2 - 600 kcmil
375
42.7
C. Panelboard Main Circuit Breaker
lb-in
N-m
Busbar-to-Breaker
90
10.2
Compression Lug
250
28.5
D. Branch Circuit Breakers
lb-in
N-m
Up to 30 Amp
35
4.0
40 to 100 Amp
45
5.1
E. Terminal Block Compression Lug
AWG Wire Size or Range
lb-in
N-m
#14 - #10
35
4.0
#8
40
4.5
#6 - #00
120
13.6
#6 - 350 kcmil
275
31.1
#4 - 500 kcmil
375
42.4
Summary of Contents for Datawave
Page 2: ......
Page 6: ...2 Figure i Typical Datawave Magnetic Synthesizer Equipment Arrangement...
Page 17: ...Installation Instructions 13 Figure 8 Datawave Bypass Configuration 100 200 kVA...
Page 20: ...16 Installation Instructions Figure 9 Typical Junction Box Connections...
Page 24: ...20 Installation Instructions Figure 11 Intermodule Wiring 150 200 kVA...
Page 27: ...Installation Instructions 23 Figure 13 Typical Control Wiring for Units Without Monitoring...
Page 28: ...24 Installation Instructions Figure 14 Typical Control Wiring for Units With Monitoring...
Page 44: ...40 Maintenance...