Licht
http://www.licht-labs.com
Rev. A2 (23–01–09)
MFC-200/P Technical Manual
15
A Specifications
Power Supply
Isolated, 80-260 Vac/Vdc.
Power Consumption
8 W
Operating Temperature
-20 to 70
◦
C (LCD display)
-40 to 85
◦
C (VFD display)
Enclosure Rating
IP20
Mounting Options
35 mm DIN Rail
Tap Measurement Inputs
2-wire Potentiometric
Current (e.g.: 4-20 mA)
Voltage (e.g.: 0-10 V)
Number of Positions
2 to 50
Potentiometric Disc Resistance
8 to 1000 Ω
Resistance per Tap
4 to 20 Ω
Dimensions (L x H x D)
100 x 75 x 110 mm
Weight
1.0 kg
DC Scales
0-1, 0-5, 0-10, 0-20, 4-20 mA
Error/Non-linearity (inputs)
0.2% + 0.1%
/
10
◦
C
Error/Non-linearity (outputs)
0.2% + 0.1%
/
10
◦
C
Galvanic Isolation
(60
Hz
, 1 min.)
Outputs
2.0
kV
Communication
2.0
kV
Communication
RS-485 - MODBUS RTU or DNP3
9600, 19200, 38400, 57600, 115200 bps
8N1, 8E1, 8O1, 8N2
Displays
2 lines, 16 characters each (5 mm).
LCD with backlight or VFD.
Relays
10 A @ 250 Vac, 0.5 A @ 125 Vdc
Galvanic Isolation: 2.0 kV, 60 Hz, 1 min.