Licht MFC-200/P Technical Manual Download Page 14

Licht

http://www.licht-labs.com

[email protected]

Rev. A2 (23–01–09)

MFC-200/P Technical Manual

13

6 Error conditions

6.1 Synchronism error

Synchronism errors occur whenever one or more Follower on-load tap changers stop fol-

lowing their Master, despite commands to do so. These may occur between 3-phase

transformers or phases of a 3-phase group of monophase transformers.

Synchronism errors are only set after the user-configurable Syncronism Timeout expires.

Possible causes:

.

Connection failure between the raise/lower voltage regulator and the tap changer.

.

Tap changer failure, preventing it from receiving and/or executing position changes.

.

An Individual transformer is incorrectly configured as Follower.

.

The position was manually altered at the tap changer and not through the paral-

lelism controller.

6.2 Position deviation

Position deviations are characterized by readings which shift considerably from their ideal

value. Despite not being large enough to be interpreted as another position altogether,

they suggest failure or imminent failure of the position transducer element, either due to

calibration, tap changer failure or connection problem.

Possible causes:

.

EMI (electro-magnetic interference) due to faulty or lack of cable shielding.

.

EMI due to failure to ground the cables’ shielding.

.

Shielding grounded at more than one point.

.

Contact problem.

.

Failure to recalibrate after changing cables.

6.3 Configuration error

Configuration errors may occur in the following scenarios:

.

Follower channels without a Master.

.

Master channel with no Followers.

.

More than one Master.

Summary of Contents for MFC-200/P

Page 1: ...Parallelism Controller model MFC 200 P Technical Manual Licht...

Page 2: ...er reset 8 5 Programmable parameters 9 5 1 MODBUS protocol 10 5 2 DNP3 protocol option 11 6 Error conditions 13 6 1 Synchronism error 13 6 2 Position deviation 13 6 3 Configuration error 13 6 4 Commun...

Page 3: ...rom its potentiometric sensor or indirectly either via a current loop typically 4 20 mA or BCD contacts according to the client s specifications During parallel control the Master tap changer s positi...

Page 4: ...without network option 3 MFC 200 P b controls a 3 phase bank of monophase transformers possibly net worked with other MFC 200 P 1 or MFC 200 P b devices Communication functionality with supervisor sy...

Page 5: ...oltage Circulation currents are minimized by operating transformers on identical positions In the Master Follower principle a transformer which we denote the Master is chosen as the reference The othe...

Page 6: ...lence Group 3 phase Transformer is only lost when a group is set as Disabled Otherwise the MFC 200 P will always attempt to maintain a group s 3 phases in the same numerical position Master Phase A Po...

Page 7: ...lways a bank s reference phase which phases B and C automatically follow Whenever the MFC 200 P is configured for 3 phase transformers the channel s position is always displayed If configured for a ba...

Page 8: ...sssage will be displayed and the command will be ignored Next press the P key and select Manual Command in the configuration menu Select the transformer to be commanded 1 or 2 and press P The command...

Page 9: ...anger to its minimal position When the value stabilizes press the P key 3 The message Max Tap A Phase will be displayed along with a value proportional to phase A s measured resistance Take the tap ch...

Page 10: ...n Selects the parallelism mode for transformers 1 and 2 Number of Positions Options 2 to 50 Description The on load tap changer s number of positions Synchronism Error Timeout Options 5 to 100 s Descr...

Page 11: ...Error Transformer or group Open Closed Any MFC 200 P Open Closed Communication Error Transformer or group Open Closed Any MFC 200 P Open Closed Position Deviation Transformer or group Open Closed Any...

Page 12: ...parity 1 stop bit 8N2 8 data bits no parity 2 stop bits Parameter Address Options 0x0000 to 0xFFEF Description DNP3 outstation address in hexadecimal notation Parameter Application Layer Confirmation...

Page 13: ...the line to become idle Once that happens it waits for Tdelay Tfixed Trandom ms where Tfixed is the fixed backoff delay and Trandom is a random value uniformly distributed between 0 and the random ba...

Page 14: ...nfigured as Follower The position was manually altered at the tap changer and not through the paral lelism controller 6 2 Position deviation Position deviations are characterized by readings which shi...

Page 15: ...P is responsible for a given transformer or group and they must exchange position information to correctly operate Possible causes for communication errors are More than one MFC 200 P set to the same...

Page 16: ...0 10 V Number of Positions 2 to 50 Potentiometric Disc Resistance 8 to 1000 Resistance per Tap 4 to 20 Dimensions L x H x D 100 x 75 x 110 mm Weight 1 0 kg DC Scales 0 1 0 5 0 10 0 20 4 20 mA Error N...

Page 17: ...Licht http www licht labs com info licht labs com Rev A2 23 01 09 MFC 200 P Technical Manual 16 B Housing...

Page 18: ...Licht http www licht labs com info licht labs com Rev A2 23 01 09 MFC 200 P Technical Manual 17 C Connection diagrams...

Page 19: ...Licht http www licht labs com info licht labs com Rev A2 23 01 09 MFC 200 P Technical Manual 18...

Page 20: ...Licht http www licht labs com info licht labs com Rev A2 23 01 09 MFC 200 P Technical Manual 19...

Page 21: ...Licht http www licht labs com info licht labs com Rev A2 23 01 09 MFC 200 P Technical Manual 20...

Page 22: ...conduits must be preserved up to frequencies in the order of MHz over all their extension including curves and junctions In order to guarantee this continuity joints and bonds should present electric...

Page 23: ...o licht labs com Rev A2 23 01 09 MFC 200 P Technical Manual 22 i RS 485 devices must be connected in a bus topology No other network topology tree star ring etc is acceptable j Dry contact inputs if a...

Page 24: ...ster Follower Individual Disabled Number of Positions 2 to 50 Synchronism Error Timeout 5 to 100 s Configuration Error Timeout 5 to 100 s Address 0 to 15 Output Current 0 1 0 5 0 10 0 20 4 20 mA Relay...

Page 25: ...sabled Transformer 2 Mode Master Follower Individual Disabled Number of Positions 2 to 50 Synchronism Error Timeout 5 to 100 s Configuration Error Timeout 5 to 100 s Output Current 0 1 0 5 0 10 0 20 4...

Page 26: ...0 1 mA 1 0 5 mA 2 0 10 mA 3 0 20 mA 4 4 20 mA 1 8 Relay 12 Configuration See section 5 1 9 Relay 13 Configuration See section 5 1 10 Relay 14 Configuration See section 5 1 101 read only Transformer 1...

Page 27: ...n 5 1 8 Relay 13 Configuration See section 5 1 9 Relay 14 Configuration See section 5 1 101 read only A Transformer s Position 2 to 50 1 102 read only B Transformer s Position 2 to 50 1 103 read only...

Page 28: ...Licht http www licht labs com info licht labs com Rev A2 23 01 09 MFC 200 P Technical Manual 27...

Reviews: