Installation of Preset Level Sensor Holder

Side Wall 

Mount

Figure 5

Discharge Pipe 

Mount

Page 3 of 6

Operation and Maintenance Manual

7000 Apple Tree Avenue, Bergen, NY 14416 Phone: (800) 543-2550-Fax: (585) 494-1839-www.libertypumps.com

Pump

Start

High Level

Probe

High Level

Float

 5

 1  2  3  4

 6  7

Auxiliary Contacts 

24VDC, 1A

Conect to Remote Alarm

Or BAS/SCADA System

Off

Probe

Start

Probe

Alarm

Probe

Float Float

Circuit Board

 Green

 Y

ellow

 Red

 White

 Black

5 Conductor Cable from 

Preset Level Sensor

Figure 6

Figure 4

DWG#7235000G

Manual 7235000G

Off

Probe

Operation and Maintenance Manual

Operation and Maintenance Manual

1.  Review figures 4, 5 and 6.

2.  Attach sensor holder to discharge pipe or separate pipe (mounted to side wall) using the stainless  

 

 

     steel pipe clamp. Make sure sensor is clear of inlet water and at least 1” to 2” away from any conductive  

                     

     material. Make sure the bottom probe (off level) is at the same height as the top of the pump or just slightly  

 

     below ensuring submergence of the pump. See figure 5.

3.  Route the five conductor cable to the control panel through the liquid tight cord connector and tighten    

 

     compression nut.

4.  Connect the wires from the level sensor to the terminal strip inside the control panel. See figure 6.

5.  If splicing on sensor cable is required:
     

A. For any splicing longer than 100 feet, consult factory.

      B. Use liquid tight junction boxes and appropriate liquid tight  

 

 

 

     

 

 

      

          connectors and/or conduit.

      C. Do not mix high and low voltage circuits in same junction box.

      D. For level sensor splice, it is recommended to use 5 conductor,

          18 AWG shielded cable.  Only ground the shield on one end of 
          the cable – easiest to ground shield wire in panel to the ground 

lug.

Preset Level 

Sensor Holder 