6
Convertible Air Conditioner
Installation of Indoor, Outdoor Unit
3) Piping length and the elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the basis of
reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
CAUTION
Model
LV-C286BLA1 5/8"(15.88mm) 1/4"(6.35mm)
7.5
30
5
20
25
LV-H246BLA1 5/8"(15.88mm) 1/4"(6.35mm)
7.5
30
5
20
40
LV-C362KLA0 5/8"(15.88mm) 1/4"(6.35mm)
5
20
5
30
25
LV-C602LLA0 3/4"(19.05mm) 3/8"(9.52mm)
7.5
20
5
30
60
LV-C60BLLA0 3/4"(19.05mm) 3/8"(9.52mm)
7.5
20
5
30
50
LV-C602LLA2 3/4"(19.05mm) 3/8"(9.52mm)
7.5
20
5
30
50
*Additional
refrigerant(g/
m)
Pipe Size
(Diameter:Ø)
Length A(m)
Elevation B(m)
Standard
Max.
Standard
Max.
Gas
Liquid