background image

- 2 -

Copyright ©2010 LG Electronics. Inc. All right reserved.
Only for training and service purposes

LGE Internal Use Only

1. Specification

Indoor

Power Supply

Ø / V / Hz

Current

Nominal Running Current

A

Fan

Motor Type

Fan Type

Motor Output(W) x No. of Unit

Air Flow Rate 

CMM

(H / M / L)

cfm

External Static Pressure

mmAq

Capacitor

μF / Vac

Drive

Coil

Row x Column x FPI

Dimensions Body

mm(inch)

(W x H x D)

Decorative Panel

mm(inch)

Net Weight

Body

kg (lbs)

Decorative Panel

kg (lbs)

Sound Level (H / M / L)

dB(A)+3

Piping

Liquid

mm (inch)

Connections

Gas

mm (inch)

Drain(OD/ID)

mm

Dehumidification Rate

l/h

Safety Devices

Temperature Sensor

Referigerant

Referigerant Control

Connectable Outdoor Unit

Power and Transmission Interunit Cable

No. x mm

2

Indoor Unit Type

Model

Decorative Panel Model

Ceiling Suspended type

UVNH36GLLA1

-

1/220-240/50

0.67 x 2

BLDC

Sirocco Fan

154 x 2

28.6 / 26.9 / 25.2

1010 / 950 / 890

-

-

Direct Drive

3R x 14C x 17FPI

1750 x 220 x 650 (68.9 x 8.7 x 25.6)

-

45 (99.2)

-

44 / 42 / 40

9.52 (3/8)

15.88 (5/8)

20/16

2.93

Fuse

Thermistor

R410A

EEV (Outdoor Unit)

AUUW366DH1

4 x 0.75 (included earth)

Note:

1. Capacities are based on the following conditions:

Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB

- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB

Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB

- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB

Piping Length - Interconnecting Piping Length 5.0m

- Level Difference of Zero

2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.

Conversion Formula
kW  = Btu/h x 0.0002931
cfm = CMM x 35.3

Summary of Contents for UVNH36GLLA1

Page 1: ...xploded View Type Ceiling Suspended Air conditioner MODEL UVNH36GLLA1 CAUTION Before Servicing the unit read the safety precautions in General SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com ...

Page 2: ... mm2 Indoor Unit Type Model Decorative Panel Model Ceiling Suspended type UVNH36GLLA1 1 220 240 50 0 67 x 2 BLDC Sirocco Fan 154 x 2 28 6 26 9 25 2 1010 950 890 Direct Drive 3R x 14C x 17FPI 1750 x 220 x 650 68 9 x 8 7 x 25 6 45 99 2 44 42 40 9 52 3 8 15 88 5 8 20 16 2 93 Fuse Thermistor R410A EEV Outdoor Unit AUUW366DH1 4 x 0 75 included earth Note 1 Capacities are based on the following conditio...

Page 3: ...ly 2 Piping Diagrams Indoor Unit Th2 Th3 Th2 Th1 Heat Exchanger Cooling Heating Sirocco Fan LOC Description PCB Connector Th1 Thermistor for inlet air temperature CN_ROOM Th2 Thermistor for EVA in temperature CN_PIPE IN Th3 Thermistor for EVA out temperature CN_PIPE OUT Model Gas mm Liquid mm UVNH36GLLA1 15 88 9 52 ...

Page 4: ...cs Inc All right reserved Only for training and service purposes LGE Internal Use Only 3 Wiring Diagrams CN_DISPLAY CN_DOOR CN_OPTION CN_VANE1 CN_VANE2 CN_MOTOR1 CN_MOTOR2 CN_POWER CN_ROOM CN_PIPE OUT CN_PIPE IN CN_VM CN_REMO CN_CC ...

Page 5: ...ternal Use Only Indoor Unit 4 Exploded View 137211 135310 354210 352118 552111 146811 336600A 430410 267110 249310 261704 137213A 249951 346810 W48602 137213B 135515A 159830 237205 349600 348601 359012 147901 336600B 135515B 263230C 263230A 263230B 268711C 268711A 268711D 268711B 249951A 330871 135303 ...

Page 6: ...P NO MFL67104203 DECEMBER 2010 ...

Reviews: