8
INSTALLATION OF OUTDOOR UNIT
ENGLISH
• Synchro Operation
Install the branch pipe so that pipe length and difference between high and low will not exceed
below Spec.
• Refrigerant Additional Charging Method
For additional charging method, see below table.
- When installing the branch pipe, direction and angle of installation is not limited.
- Take care so that burrs and foreign material may not enter into the cutting surface when con-
necting.
- Connect remaining those by cutting or direct insertion to the diameter of pipe.
[Unit : m]
Branch
L1
H1
A
A
L2
L3
L4
L5
H2
Remote
Controller
Pipe Length & Height
Spec(MAX.)
Total(L1+L2+L3+L4+L5)
Main Pipe(L1)
Branch Pipe (L2+L3+L4+L5)
Each
Indoor-Outdoor (H1)
Indoor-Indoor (H2)
(L1+L2),(L1+L3),(L1+L4),(L1+L5)
A
80
40
40
10
30
1
70
10
Indoor Unit
Refrigerant Additional charging (g)
Duo
Refrigerant = (L1-b) x B + (L2 + L3) x C
Trio
Refrigerant = (L1-b) x B + (L2 + L3 + L4) x C
Quartet
Refrigerant = (L1-b) x B + (L2 + L3 + L4 + L5) x C
Model
b (mm)
B(g/m)
UU70W
25
70
Pipe Diameter.
(mm)
C (g/m)
Ø 6.35
35
Ø 9.52
40
NOTE
!
b : Rated performance for refrigerant line length.
C : Additional charging Refrigerant of Branch Liquid Pipe.
B : Additional charging Refrigerant of Main Liquid Pipe.
CAUTION
• Capacity is based on standard length and maximum allowance length is on the basis of re-
liability.
• Improper refrigerant charge may result in abnormal cycle.
!
1.MFL68645302(영) 16. 12. 7. 영영 6:09 Page 8