INSTALLATION METHOD
ENGLISH
15
WARNING
Followings should be kept before wiring.
• Supply type of electric heater should be ensured.
• Never connect electric power while wiring electric heater.
• The wire that is connected to electric heater should be used to meet specification of each
country.
• Main power of electric heater should be applied with ELCB.
!
CAUTION
• Power Cable Specification : The power cord connected to the outdoor unit should be
complied with IEC 60245 or HD 22.4 S4(Rubber insulated cord, type 60245 IEC 66 or
H07RN-F)
• Connecting Cable Specification : The connecting cable connected to the outdoor unit
should be complied with IEC 60245 or HD 22.4 S4 (This equipment shall be provided with a
cord set complying with the national regulation.)
• If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons
in order to avoid a hazard.
• In order to avoid a hazard due to inadvertent resetting of the
thermal cut-out, this appliance must not be supplied through
an external switching device, such as a timer, or connected
to a circuit that is regularly switched on and off by the utility.
!
GN/
YL
20 mm
35±5 mm
10±3 mm
1 Phase(Ø)
4C
NORMAL
CROSS-SECTIONAL
AREA 0.75 mm
2
2C
NORMAL
CROSS-SECTIONAL
AREA 0.75 mm
2
Power
Supply
Capacity(kW)
Phase(Ø)
Area(mm
2
) x Cores
3
1
1.5 x 3C
6
4 x 3C
Connecting
Cable
Capacity(kW)
Purpose
Phase(Ø)
Area(mm
2
) x Cores
3
SIGNAL (Electric Heater)
1
0.75 x 2C
Sensor
0.75 x 2C
6
SIGNAL (Electric Heater)
0.75 x 4C
Sensor
0.75 x 2C