20 Room Air Conditioner
Installation
Outdoor
Align the center of the pipings and sufficiently
tighten the flare nut by hand.
Finally, tighten the flare nut with torque wrench
until the wrench clicks.
• When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
mm
inch
kgf.m
Ø6.35
1/4"
1.8~2.5
Ø9.52
3/8"
3.4~4.2
Ø12.7
1/2"
5.5~6.6
Ø15.88
5/8"
6.3~8.2
Ø19.05
3/4"
9.9~12.1
Outside diameter
Torque
Gas side piping
(Bigger diameter)
Torque wrench
Liquid side piping
(Smaller diameter)
Outdoor unit