25
INSTALLER SETTING
Air conditioner Installer setting
Function
Product
Description
Option
AIRCON Vent
Test Run
O
O
It is the function to test the operation at initial
installation.
Cool test Run / Heat Test Run
Central Control Address
O
O
Assign a unique address code of indoor units
when used with central controller.
00~FF
ESP
O
Sets the wind amount value for each fan speed. Select fan speed one by one to set each RPM value.
Temperature
Sensor(2TH)
O
O
Select which standard temperature value that
will be used to control temperature.
Remote controller / Indoor unit / 2TH
Ceiling Height Selection
O
It is the function to change the wind amount
according to the ceiling height for the ceiling
type products.
Low / Standard / High / Super High
Static Pressure
O
This function changes the fan speed in the
indoor FAN according to the opening and closing
quantity of Damper.
V-H : Indoor fan speed change, High pressure
F-H : Fixed with set fan speed, High pressure
V-L : Indoor fan speed change, Low pressure
F-L : Fixed with the set fan speed, Low pressure
Override Master/Slave
O
O
This function prevents operation of other modes.
Products set as slave can only be changed to
the operation mode of the master product.
- Unable to operate cooling and heating at the
same time
Master / Slave
Dry Contact Mode
O
O
This function activates/inactivates the dry
contact auto function.
Automatic / Manual
Fixed Air Volume
O
O
This function sets the fan speed mode of the
indoor unit to variable/fixed.
Variable
Operate to set fan speed at
COMP ON.
Operate to low fan speed at
COMP OFF.
Fixed
Operate to set fan
speed at COMP ON.
Operate to set fan
speed at COMP OFF.
Zone type
O
This function sets the type of zone controller
(New or Old) of the indoor unit.
Old
Only the operation status
of the zone using a wired
remote controller can be
checked.
New or 8 zone
Zone control and
monitoring is possible
using wired remote
controller.
Zone Number
O
Set the number of installed zones in case of
using new type of zone
2~8
Pipe Temperature
O
O
You can check the temperature of the pipe
temperature.
Func. Control During
Grp. Control
O
You can set the emergency heater usage and
environment.
Use
Outdoor
temperature
standard heater
operation
enable setting
and temperature
step value
Fan operation in
Emergency
Use
Not Use
Not use
Step1
Step2
Step3
On
Off
Function setting during
Group control
O
This function selects the operation standard of
the product when controlling the group.
Option kit installation
- Air purify / Heater
/Humidification
/ Elevationgrill /
Ventilation /Refrigerant
leakagedetection sensor
O
Please set whether to install the option kit.
Not installed / Installed
IDU Address Verification
O
O
Check the value of Auto Addressing of the
outdoor unit with the remote controller.