Setting and using method
16
Dry contact For Economizer
5) Compressor stop mode
Ú
Compressor stop mode: The compressor is stopped during cool/heat operation.
Ú
Power save mode: Adjust the set temperature to +3℃(6℉) for cooling and -3℃(6℉) for heating.
6) Operating mode selection mode
Input A
Input B
Operating mode
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Indoor unit operating (Compressor in stop mode), locked
Indoor unit prior operating condition maintained
(Compressor not in stop mode), unlocked
Indoor unit stopped, locked
Indoor unit stopped, locked
CONTROL
MODE SWITCH
B
7) Thermal off in cooling mode when interlocking with Economizer
Ú
When setting E mode, turn on 2nd switch of SETTING.
Input A
Input B
Operating mode
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Indoor unit stopped, unlocked
Indoor unit in cool/high operation, unlocked
Indoor unit in heat/high operation, unlocked
Indoor unit in fan/high operation, unlocked
Indoor unit stopped, locked
Indoor unit in cool/high operation, locked
Indoor unit in heat/high operation, locked
Indoor unit in fan/high operation, locked
CONTROL
MODE SWITCH
C
D
Input A
Input B
Operating mode
OFF
OFF
Indoor unit prior operating condition maintained, occupied, unlocked
ON
OFF
Indoor unit operating with thermal off in cooling mode, occupied, unlocked
OFF
ON
Indoor unit prior operating condition maintained, unoccupied, unlocked
ON
ON
Indoor unit prior operating with thermal off in cooling mode, unoccupied, unlocked
CONTROL
MODE SWITCH
E