Installation Manual
19
ENGLISH
Checkup before Reporting Trouble
Error Number
Error Description
Meaning
Main Cause
230
Error with detecting
refrigerant leak
Refrigerant leak
detection and sensor
failure error
1. Incorrect setting for the refrigerant leak
detector
2. Short failure of the refrigerant leak detector
terminal
3. Wrong connection of the refrigerant leak
detector
4. Failure with the refrigerant leak detector
5. Refrigerant leak detection
n
Troubleshooting
[Note 1] Check the normal state of the refrigerant leak detector.
- Normal state: The green LED light turns on or the green and red LED lights blink
at the same time.
- Failure state: The green and red lights blink alternately.
No
Does the internal sensor
of the refrigerant leak detector
work properly? [Note 1]
Yes
No
Change the sensor.
No
1. Check the installation of the main PCB CN-Leak
Short Key of the indoor unit.
2. Reset the power of the indoor unit.
3. Check that the Remote Control Setting is 29:00.
Is the connecting cable
of the refrigerant leak detector
properly connected?
Is the indoor unit of
the refrigerant leak
detector installed?
Refrigerant leak detection
Yes
Yes
1. Turn the indoor unit off.
2. Reconnect the connector.
3. Turn the indoor unit on.
LED