background image

4

IMPORTANT SAFETY INSTRUCTIONS

ENGLISH

• Do not touch the board when the power is connected. It can

cause a fire, electric shock, explosion, injury and problem to the
product.

• Unplug the unit if strange sounds, smell, or smoke comes from

it. Otherwise, it may cause electrical shock or a fire.

• The appliance must only be supplied at safety extra low voltage

corresponding to the marking on the appliance.

CAUTION

In-use

• Do not clean using the powerful detergent like solvent but use

soft cloths. It will cause fire or product deformation.

• Do not press the screen using powerful pressure or select two

buttons. It will cause product breakdown or malfunction.

• Do not touch or pull the lead wire with wet hands. It will cause

product breakdown or electric shock.

• This appliance is not intended for use by persons (including

children) with reduced physical, sensory or mental capabilities,
or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance
by a person responsible for their safety. Children should be
supervised to ensure that they do not play with the appliance.

• This appliance can be used by children aged from 8 years and

above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they have
been given supervision or instruction concerning use of the
appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user
maintenance shall not be made by children without supervision.

!

Summary of Contents for PEXPMB100

Page 1: ...L62179522 Rev 01_042419 Representative LG Electronics Inc EU Representative LG Electronics European Shared Service Center B V Krijgsman 1 1186 DM Amstelveen The Netherlands Manufacturer LG Electronics Inc Changwon 2nd factory 84 Wanam ro Seongsan gu Changwon si Gyeongsangnam do KOREA ACU IO Original instruction ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH ΕΛΛΗΝΙΚΆ ČEŠTINA NEDERLANDS POLSKI LIMBA ROMÂ...

Page 2: ... can result in hazards to you and others Installation work must be performed in accordance with the National Electric Code by qualified and authorized personnel only The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments Failure to carefully read and follow all instruction...

Page 3: ... electric shock explosion or injury Securely attach the electrical part cover to Module If the electric part cover of Module is not attached securely it could result in a fire or electric shock due to dust water etc Make the connections securely so that the outside force of the cable may not be applied to the terminals Inadequate connection and fastening may generate heat and cause a fire In use D...

Page 4: ...e lead wire with wet hands It will cause product breakdown or electric shock This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensu...

Page 5: ...U UO 1 EA Installation Manual 1 EA ACU UI 1 EA Installation Manual 1 EA NOTE This model requires external power supply DC 12 V Select an insulating transformer that complies with IEC61558 2 6 and NEC Class 2 Please check the product operation range below Power supply DC 12 V Product operation range Ambient temperature 20 65 C Humidity 0 98 Non condensing ...

Page 6: ...O PEXPMB100 ACU UI RST_2 RST_1 CN_UART 12VDC CH1 UI1 UI2 UI3 UI4 G G A B RS485 CH2 AO1 AO2 G G DO1 DO2 A B RS485 DIGITAL OUPUT ANALOG OUTPUT UNIVERSAL INPUT ON SW01 LDO1 LDO2 1 2 3 4 1 2 3 4 SW02 ON ڸ ڸ ڹ ڹ ڿ ۄ ۄ ڼ ڼ ں ں ڽ ڽ ھ ھ ڿ ڿ ۀ ۀ ۀ LDO3 LDO4 LDO5 LDO6 ۃ ۃ ۂ ہ RST_2 RST_1 CN_UART 12VDC CH1 AO1 AO2 AO3 AO4 G G A B RS485 DO1 DO2 DO3 DO4 DO5 DO6 COM COM DIGITAL OUTPUT UNIVERSAL INPUT ANALOG OUT...

Page 7: ... 2 3 4 OFF OFF OFF OFF 81 ON 1 2 3 4 OFF OFF ON OFF 82 ON 1 2 3 4 OFF ON OFF OFF 83 ON 1 2 3 4 OFF ON ON OFF 84 ON 1 2 3 4 ON OFF OFF OFF 85 ON 1 2 3 4 ON OFF ON OFF 86 ON 1 2 3 4 ON ON OFF OFF 87 ON 1 2 3 4 ON ON ON OFF Model PEXPMB100 ACU UI Address SW02 DIP S W No 1 2 3 4 70 ON 1 2 3 4 OFF OFF OFF OFF 71 ON 1 2 3 4 OFF OFF ON OFF 72 ON 1 2 3 4 OFF ON OFF OFF 73 ON 1 2 3 4 OFF ON ON OFF 74 ON 1 ...

Page 8: ...t work Turn power off before wiring and then power it on after wiring Be careful because static electricity can cause product damage during installation For the wired Power wire Communication wire and Signal wire remove the coating at the end of the wire to connect and than use the pin type JOBN153 to connect to the terminal block All field supplied parts and materials and electric works must be c...

Page 9: ... 0 Open 1 Short 2 10002 DI 2 0 Open 1 Short 3 10003 DI 3 0 Open 1 Short 4 10004 DI 4 0 Open 1 Short Input Register 0x04 No Register Data Bit Funtion 1 30001 AI 1 0 1000 0 0 10 0 V 2 30002 AI 2 0 1000 0 0 10 0 V 3 30003 AI 3 0 1000 0 0 10 0 V 4 30004 AI 4 0 1000 0 0 10 0 V Holding Register 0x03 No Register Data Bit Funtion 1 40001 AO 1 0 1000 0 0 10 0 V 2 40002 AO 2 0 1000 0 0 10 0 V ACU UO Coil Re...

Page 10: ...en 1 Short 5 10005 DI 5 Dry Contact 0 Open 1 Short 6 10006 DI 6 Dry Contact 0 Open 1 Short 7 10009 DI 1 Wet Contact 0 Open 1 Short 8 10010 DI 2 Wet Contact 0 Open 1 Short 9 10011 DI 3 Wet Contact 0 Open 1 Short Input Register 0x04 No Register Data Bit Funtion 1 30001 AI 1 0 1000 0 0 10 0 V 2 30002 AI 2 0 1000 0 0 10 0 V 3 30003 AI 3 0 1000 0 0 10 0 V 4 30004 AI 4 0 1000 0 0 10 0 V 5 30005 AI 5 0 1...