44
MultiSITE CRC 2 Controller
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
BACnet MS/TP Quick Setup
This quick set-up describes how to set-up the BACnet* MS/TP
with a Remote Controller. Please see BACnet MS/TP Configu-
ration section of the MultiSITE CRC2 User Interface Guide for
complete instructions of the configuration of the BACnet MS/TP
network.
1. Touch and hold top of the screen for 3 seconds to enter Con-
figuration settings as illustrated in Figure 7 on page 14.
2. Navigate to the “Network Config” -->”BACnet settings” menu
of the “Configuration” page.
3. Change the “COM Address.” Valid COM address range is
0-253. Note: COM address defaults to 254 which disables
BACnet MS/TP.
4. Select “Network Units” (Imperial or Metric)
5. Select appropriate BAUD Rate. Note: “Auto” is the default
setting and will auto detect baud rate of connected device.
6. Select BACnet Instance Number or use default BACnet
Instance. Note: BACnet Instance number defaults to 8300
and the COM address. Example if the COM address is 57
the BACnet Instance number will be “83057.”
7. Ensure BACnet status reads Online.
Note
If optional Wi-Fi module is used the transport will be BACnet IP
instead of BACnet MS/TP. In this case, BACnet configuration is only
accessible via a web browser. Refer to the Wi-Fi Accessory Card
installation manual for details.
BACNET MS/TP SETUP
*BACnet is a registered trademark of ASHRAE.
Summary of Contents for MultiSITE CRC2 Series
Page 49: ......