5. Indoor Unit and Outside Unit Capacity Index
7
MULTI V Water IV
Heat Pump
General information
CAUTION
•
Ratio of the running Indoor Units to the Outside: Within 10 ~ 100%
•
A combination operation over 100% cause to reduce each indoor unit capacity.
Combination ratio (50~200%)
Notes :
1.
We can guarantee the operation only within 130% Combination Ratio.
If you want to connect more than 130% combination Ratio, please contact us and discuss the
requirement.
2.
In case that operating indoor units ratio to rated capacity of Outside unit is more than 130%, the airflow
should be operated as low step in the all indoor units.
Number of Outside units
Combination Ratio
Single Unit
200 %
Two Units combination
160 %
Three or more Units combination
130 %