General Installation Guidelines
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 10: ACR Copper Tubing Dimensions and Physical Characteristics
1-4
.
Nominal Pipe
Outside
'LDPHWHULQ
Actual Outside
'LDPHWHULQ
'UDZQ7HPSHU
Annealed Temper
Nominal Wall
7KLFNQHVVLQ
:HLJKWOEIW
Cubic ft per
Linear ft
Nominal Wall
7KLFNQHVVLQ
:HLJKWOEIW
Cubic ft per
Linear ft
1/4
0.250
--
--
--
0.030
0.081
.00020
3/8
0.375
0.030
0.126
.00054
0.032
0.134
.00053
1/2
0.500
0.035
0.198
.00101
0.032
0.182
.00103
5/8
0.625
0.040
0.285
.00162
0.035
0.251
.00168
3/4
0.750
0.042
0.362
.00242
0.042
0.362
.00242
7/8
0.875
0.045
0.455
.00336
0.045
0.455
.00336
1-1/8
1.125
0.050
0.655
.00573
0.050
0.655
.00573
1
All dimensions provided are in accordance with ASTM B280 – Standard.
2
Design pressure = 551 psig.
3
ACR Tubing is available as hard drawn or annealed (soft) and are suitable for use with R410A refrigerant.
4
The Copper Tube Handbook, 2010, Copper Development Association Inc., 260 Madison Avenue, New York, NY 10016.
• Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert gas.
• Prevent dust, water or other contaminants from entering the piping during installation. Contaminants can cause mechanical failure.
LG Engineered Y-branch Kits and Header Kits
LG Y-branch and Header kits are highly engineered devices designed to evenly divide the flow of refrigerant, and are used to join one pipe
segment to two or more segments.
No Substitutions
2QO\/*VXSSOLHG<EUHDGHU¿WWLQJVFDQEHXVHGWRMRLQRQHSLSHVHJPHQWWRWZRRUPRUHVHJPHQWV7KLUGSDUW\RU¿HOGIDEULFDWHG
7HH¶V<¿HDGHUVRURWKHUEUDQFK¿WWLQJVDUHQRWTXDOL¿HGIRUXVHZLWK/*0XOWL96V\VWHPV7KHRQO\¿HOGSURYLGHG¿WWLQJVDOORZHGLQ
a Multi V S piping system are 45° and 90° elbows.
Table 11: Y-Branches and Headers.
Y-branch Kit Model No
Headers
4 branch
7 branch
ARBLN01621
ARBL054
ARBL057
ARBLN03321
ARBL104
ARBL107
• If the diameter of the branch pipe segments differ from that of the designated refrigerant piping, trim to the desired section using a pipe
cutter, and then use an adapter to connect.
•
$OZD\VIROORZPDQXIDFWXUHU¶VJXLGHOLQHVRQUHIULJHUDQWSLSLQJUHVWULFWLRQVVXFKDVPD[LPXPOHQJWKHOHYDWLRQGLIIHUHQFHDQGGLDPHWHUV
Failure to do so can result in reduced heating / cooling performance or equipment malfunction.
Y-Branch Kits
LG Y-branch and kits are highly engineered devices designed to evenly divide the flow of refrigerant, and are used to join one pipe seg-
PHQWWRWZRRUPRUHVHJPHQWV7KHUHLVRQO\RQHW\SHRI<EUDQFKXVHGLQ/*0XOWL6V\VWHPV<EUDQFKHVXVHGZLWKWKHLQGRRUXQLWVLQWKH
refrigerant piping system at each transition. Field-supplied “T” fittings or “Y” branches will not be accepted.
Do not install Y-branches
EDFNZDUGVUHIULJHUDQWIORZFDQQRWPDNH8WXUQVWKURXJK<EUDQFKHV7KHHTXLYDOHQWSLSHOHQJWKRIHDFK<EUDQFKƍPXVWEHDGGHGWR
each pipe segment entered into LATS piping design software.
LG Y-Branch Kits Consist of:
• Y-branches: For heat pump systems - one liquid line and one vapor line (two [2] total).
• Reducer fittings as applicable.
•
0ROGHGFODPVKHOOW\SHSHHODQGVWLFNLQVXODWLRQFRYHUV
Install Correctly
• Y-branches can be installed upstream between the Header and the outdoor unit, but a Y-branch cannot be installed between a header
and an indoor unit.
• To avoid the potential of uneven refrigerant distribution through a header fitting, minimize the difference in equivalent pipe length be-
tween the header fitting and each connected indoor unit.
Piping Preparation
GENERAL INSTALLATION GUIDELINES