22
INSTALLATION
ENGLISH
Main function of SW01D
1) Selection of the Valve Group Control
NOTE
!
If the large capacity indoor units are installed, below Y branch pipe should be used.
NOTE
!
Use the Valve Group Control when 2 branches are connected with only 1 indoor unit which
has higher capacity than 61 kBTU.
Models
Low Pressure Gas Pipe
Liquid pipe
High Pressure Gas Pipe
ARBLB03321
413
390
I.D 19.05
I.D 19.05
I.D 19.05
I.D 12.7
I.D 12.7
70
I.D 15.88
I.D 15.88
I.D 25.4
I.D 25.4
O.D 25.4
80
110
83
1
2
3
3
O.D 19.05
O.D 19.05
1
2
I.D 22.2
I.D 22.2
I.D 22.2
I.D 28.58
I.D 12.7
I.D 12.7
I.D 12.7
74
332
321
I.D 6.35
I.D 6.35
I.D 9.52(3/8)
I.D 9.52
I.D 9.52
I.D 15.88
I.D 12.7
I.D 12.7
70
I.D 25.4
110
I.D 19.05
I.D 19.05
2
3
2
3
O.D 15.88
444
421
96
I.D 15.88
I.D 22.2
I.D 22.2
I.D 22.2
O.D 15.88
I.D 19.05
I.D 9.52
h
Y branch pipe
[Unit : mm(inch)]
Valve Group
SW01D
Setting
Valve Group
SW01D
Setting
Not control
0
No. 5,6/7,8 Valve Control
8
No. 1,2 Valve Control
1
No. 1,2/5,6 Valve Control
9
No. 2,3 Valve Control
2
No. 1,2/7,8 Valve Control
A
No. 3,4 Valve Control
3
No. 3,4/5,6 Valve Control
B
No. 5,6 Valve Control
4
No. 3,4/7,8 Valve Control
C
No. 6,7 Valve Control
5
No. 1,2/3,4/5,6 Valve Control
D
No. 7,8 Valve Control
6
No. 1,2/3,4/6,7 Valve Control
E
No. 1,2/3,4 Valve Control
7
No. 1,2/3,4/7,8 Valve Control
F
* Master Only