53
ENGLISH
Function setting
Setting
Frequency (Hz)
oFF
-
op1
143 Hz
op2
135 Hz
op3
128 Hz
op4
120 Hz
op5
113 Hz
op6
105 Hz
op7
98 Hz
op8
90 Hz
op9
83 Hz
MAX. RPM Limit Setting
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn13” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”~“op7” Push the ‘
●
’ button
ODU Fan Max. RPM Limit Mode is set
Chassis
UXA
UXB
Fan MAX. RPM
Limit (RPM)
oFF
880
1 000
oP1
-20
-50
oP2
-40
-100
oP3
-60
-150
oP4
-80
-200
oP5
-100
-250
oP6
-120
-300
oP7
-140
-350
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn 12” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”,“op9” Push the ‘
●
’ button
Cool & Heat Selection mode is set
SLC(Smart Load Control) Mode
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn14” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”~“op3” Push the ‘
●
’ button
SLC(Smart Load Control) Mode is set
Setting
Mode
Detail of function
oFF
Not Setting
-
oP1
Smooth Mode
Slowly control, a target pressure value
oP2
Normal Mode
Normal control, a target pressure value
oP3
Peak Mode
Fast control, a target pressure value
Mode setting
- on:using humidity sensor
- oFF:not setting
<Using of humidity sensor>
- When used cooling operation of SLC function,it will improve energy
effcience because evaporation temperature wll be decreased
- When used heating operation in case of high humidity condition,
deforest will be delayed because target high/low pressure will be
changed.
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn16” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“on” Push the ‘
●
’ button
Humidity Reference Control mode is set
Humidity Reference Control (Fn 16)
Mode setting method
SLC (Smart Load Control) (Fn 14)
Function for set the variable target pressure which for the high
efficiency and comport operation depend on ODU load.
Mode setting method
ODU Fan Max. RPM Limit (Fn 13)
Mode setting method
Compressor Max. Frequency Limit (Fn 12)
Mode setting method
CAUTION
!
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.