Installation Manual 33
ENGLISH
33
Outdoor Unit
Refrigerant piping installation
Example : 6 indoor units connected
: Outdoor unit
: 1st branch
: Indoor units
: Sealed piping
L150m
40m
◆
Header Method
Branch pipe can not be used after header
Example : 6 indoor units connected
: Outdoor unit
: 1st branch
: Indoor unit
: Sealed piping
: Connection branch pipe
between outdoor units:
ARCNN30
: Connection branch pipe
between outdoor units:
ARCNN20
10m or
less
L150m
40m
Longest pipe length
* Equivalent pipe length
A+f
≤
150m
A+f
≤
175m
Longest pipe length after 1st branch
f
≤
40m
Difference in height(outdoor unit
↔
indoor unit)
H
≤
50m (40m : outdoor unit is lower)**
Difference in height (indoor unit
↔
indoor unit)
h
≤
15m
L
l
H
h
➲
Total pipe length = A+a+b+c+d+e+f
≤
300m
WARNING
Pipe lengths after header branch-
ing (a~f)
It is recommended that difference
in lengths of the pipes connected
to the indoor units is minimized.
Performance difference between
indoor units may occur.
CAUTION
• * : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• ** : Indoor unit should be installed at lower position than the header.
• Piping length from outdoor branch to outdoor unit
≤
10m, equivalent length : max 13m
(for 16HP or more)