Electric Characteristics
- 8 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
6. Electric Characteristics
6.1 HR Units
Symbols:
MCA: Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA ≤ 4 x FLA
(Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the MCA.
5. Instead of fuse, use Circuit Breaker.
Units Power
Supply
IFM
Input(W)
Model Hz
Volts
Voltage
Range
MCA
MFA
kW
FLA
Cooling
Heating
PRHR021
50
220
Max: 242
Min: 198
0.1
15
-
-
14
14
PRHR031
0.15
15
-
-
21
21
PRHR041
0.2
15
-
-
28
28
Units Power
Supply
IFM
Input(W)
Model Hz
Volts
Voltage
Range
MCA
MFA
kW
FLA
Cooling
Heating
PRHR021A
60
208/230
Max: 252
Min: 187
0.1
15
-
-
14
14
PRHR031A
0.15
15
-
-
21
21
PRHR041A
0.2
15
-
-
28
28