88
ELECTRICAL WIRING
Checking procedure of limiting concentration
Check limiting concentration along following steps and take appropriate measure depending on
the situation.
Calculate amount of all the replenished refrigerant (kg) per each refrigerant system.
Calculate minimum room capacity
Calculate room capacity by regarding a portion as one room or the smaller room.
- Without partition
- With partition and with opening which serve
as passage of air to adjoining room
Limiting concentration is the limit of Freon gas concentration where immediate measures can
be taken without hurting human body when refrigerant leaks in the air. The limiting
concentration shall be described in the unit of kg/m
3
(Freon gas weight per unit air volume)
for facilitating calculation.
Limiting concentration: 0.44 kg/m
3
(R410A)
Amount of additional
replenished refrigerant
Total amount of replenished
refrigerant in refrigerant
facility (kg)
+
=
Note : In case one refrigerant facility is
divided into 2 or more refrigerant
systems and each system is
independent, amount of replenished
refrigerant of each system shall be
adopted.
Amount of replenished
refrigerant per one outdoor
unit system
Amount of replenished
refrigerant at factory shipment
Amount of additionally
replenished refrigerant
depending on piping
length or piping
diameter at customer
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Opening
Partition
In the case of opening
without door , or 0.15
% or more openings
(to floor space) both
above and below door)
Outdoor unit
(No.1 system)
Flow of
refrigerant
Indoor unit
Room where refrigerant leaks
(Refrigerant of the whole No.1
system flows out.)
The installer and system specialist shall secure safety against leakage according to local
regulations or standards.
The following standards may be applicable if local regulations are not available.
Introduction
Though the R410A refrigerant is harmless and incombustible itself , the room to equip the air
conditioner should be large to such an extent that the refrigerant gas will not exceed the limiting
concentration even if the refrigerant gas leaks in the room.
Limiting concentration
CAUTION FOR REFRIGERANT LEAK
Summary of Contents for MULTI V JRUV220LTE5
Page 2: ......
Page 3: ......
Page 4: ......
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ...Simple Central Controller ACP AC Manager ...
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 79: ......
Page 84: ...84 ELECTRICAL WIRING ...
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......