INSTALLATION GUIDE FOR HAR-
MONICS AND FLICKER
The below Installation guide is limited applicable only for model
Model : ARWN140LAS4, ARWN120LAS4, ARWN100LAS4,
ARWN080LAS4
Installation Guide for Harmonics (EN 61000-3-2 & EN 61000-3-12)
Installation Guide for Flicker (EN 61000-3-3 & EN 61000-3-11)
This equipment complies with IEC (EN) 61000-3-2.
This equipment complies with IEC (EN) 61000-3-12 in harmonic
currents emission limits corresponding Rsce =33.
This equipment complies with IEC (EN) 61000-3-12 provided that
the short-circuit power Ssc is greater than or equal to 4671 kVA at
the interface point between the user’s supply and the public sys-
tem. It is the responsibility of the installer or user of the equipment
to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to 4671 kVA.”
This equipment complies with IEC (EN) 61000-3-3.
This equipment complies with reference impedance for IEC (EN)
61000-3-11.
This device is intended for the connection to a power supply sys-
tem with a maximum permissible system impedance
Z
MAX
of
Ω
at the interface point (power service box) of the
user’s supply. The user has to ensure that this device is connected
only to a power supply system which fulfills the requirement
above. If necessary, the user can ask the public power supply com-
pany for the system impedance at the interface point.
The below Installation guide is limited applicable only for model
Model : ARWN200LAS4, ARWN180LAS4, ARWN160LAS4
Installation Guide for Harmonics (EN 61000-3-2 & EN 61000-3-12)
Installation Guide for Flicker (EN 61000-3-3 & EN 61000-3-11)
This equipment complies with IEC (EN) 61000-3-2.
This equipment complies with IEC (EN) 61000-3-12 in harmonic
currents emission limits corresponding Rsce =33.
This equipment complies with IEC (EN) 61000-3-12 provided that
the short-circuit power Ssc is greater than or equal to 5409 kVA at
the interface point between the user’s supply and the public sys-
tem. It is the responsibility of the installer or user of the equipment
to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to 5409 kVA.”
This equipment complies with IEC (EN) 61000-3-3.
This equipment complies with reference impedance for IEC (EN)
61000-3-11.
This device is intended for the connection to a power supply sys-
tem with a maximum permissible system impedance
Z
MAX
of
Ω
at the interface point (power service box) of the
user’s supply. The user has to ensure that this device is connected
only to a power supply system which fulfills the requirement
above. If necessary, the user can ask the public power supply com-
pany for the system impedance at the interface point.