PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
ENGLISH
This function is used for creating vacuum in the system after compressor replacement, ODU
parts replacement or IDU addition/replacement.
Vacuum mode setting method
Vacuum mode off method
CAUTION
ODU operation stops during vacuum mode. Compressor can't operate.
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“SVC” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button : :
“Se3” Push the ‘
●
’ button
Start the vacuum mode : “VACC”
ODU V/V open
ODU EEV open
IDU EEV open
Dip switch off and push the reset button on PCB
!
Vacuum Mode
DIP SWITCH
7-Segment
SW01C ( : confirm)
SW02C ( : backward)
: forward)
SW04C ( X : cancel)
SW01D (reset)
SW03C (
ȭ
ȯ
Ɨ