PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
35
ENGLISH
Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit
total capacity [kW(Btu/h)]
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
≤
5.6(19,100)
Ø6.35(1/4)
Ø12.7(1/2)
< 16.0(54,600)
Ø9.52(3/8)
Ø15.88(5/8)
≤
22.4(76,400)
Ø9.52(3/8)
Ø19.05(3/4)
< 36.4(124,200)
Ø9.52(3/8)
Ø22.2(7/8)
Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
total capacity(HP)
Liquid pipe [mm(inch)]
Gas pipe [mm(inch)]
8
Ø9.52(3/8)
Ø19.05(3/4)
10
Ø9.52(3/8)
Ø22.2(7/8)
12
Ø12.7(1/2)
Ø28.58(11/8)
1,MFL67798027,영영 2018. 6. 18. 영영 3:07 Page 35