6
ENGLISH
During the installation of the unit, consider service, inlet, and outlet
acquire the minimum space as shown in the figures below.
Side space should be more than 49 mm for operating of Auto Dust Re-
moval mode.
Limita-
tions
on the
height
of the
wall
(Refer
to 4
side
walls)
h2
h1
1500 (5
9
)
Inlet
side
A
B
5050
0
(19
-11/
16
’’)
(19
-11
/16
’’)
500
(19
-11/
16
’’)
Front
side
50
0
(19
-11
/16
’’)
240
(9-1/2’’)
or more
50 (2) or more
45° or
more
• The height of the wall on the front side must
be 1500 mm (59 inch) or less.
• The height of the wall on the inlet side must
be 500 mm (19-11/16’’) or less.
• There is no limit to the wall on Inlet side.
• If the height of the walls on the front and Inlet
side are higher than the limit, there must be
additional space on the front and the side.
- Additional Space on the front side by 1/2 of
h1
- Additional Space on the inlet side by 1/2 of
h2
- h1 = A(Actual height) - 1500 (59 inch)
- h2 = B(Actual height) - 500 (19-11/16’’)
Individual Installation
INSTALLATION SPACE
Category
Installation Space
Case 1
(10mm(13/32inch)
≤
Side
Space
≤
49mm(13/14inch))
Case 2
(Side Space
≥
49mm(13/14inch))
4 sides
are
walls
A
≥
10 (13/32)
B
≥
300 (11-13/16)
C
≥
10 (13/32)
D
≥
500 (19-11/16)
A
≥
50 (1-31/32)
B
≥
100 (3-15/16)
C
≥
50 (1-31/32)
D
≥
500(19-11/16)
A
≥
10 (13/32)
B
≥
300 (11-13/16)
C
≥
10 (13/32)
D
≥
500 (19-11/16)
E
≥
20 (25/32)
A
≥
50 (1-31/32)
B
≥
100 (3-15/16)
C
≥
50 (1-31/32)
D
≥
500 (19-11/16)
E
≥
100 (3-15/16)
A
≥
10 (13/32)
B
≥
300 (11-13/16)
C
≥
10 (13/32)
D
≥
500 (19-11/16)
E
≥
20 (25/32)
F
≥
600 (23-5/8)
A
≥
50 (1-31/32)
B
≥
100 (3-15/16)
C
≥
50 (1-31/32)
D
≥
500 (19-11/16)
E
≥
100 (3-15/16)
F
≥
500 (19-11/16)
A
≥
10 (13/32)
B
≥
300 (11-13/16)
C
≥
10 (13/32)
D
≥
300 (11-13/16)
E
≥
20 (25/32)
F
≥
500 (19-11/16)
A
≥
50 (1-31/32)
B
≥
100 (3-15/16)
C
≥
50 (1-31/32)
D
≥
100 (3-15/16)
E
≥
100 (3-15/16)
F
≥
500 (19-11/16)
Rear
to
Rear
A
≥
10 (13/32)
B
≥
500 (19-11/16)
C
≥
10 (13/32)
D
≥
500 (19-11/16)
F
≥
900 (35-7/16)
A
≥
50 (1-31/32)
B
≥
500 (19-11/16)
C
≥
50 (1-31/32)
D
≥
500 (19-11/16)
F
≥
600 (23-5/8)
A
≥
10 (13/32)
B
≥
500 (19-11/16)
C
≥
10 (13/32)
D
≥
500 (19-11/16)
E
≥
20 (25/32)
F
≥
1200 (47-1/4)
A
≥
50 (1-31/32)
B
≥
500 (19-11/16)
C
≥
50 (1-31/32)
D
≥
500 (19-11/16)
E
≥
100 (3-15/16)
F
≥
900 (35-7/16)
A
≥
10 (13/32)
B
≥
500 (19-11/16)
C
≥
10 (13/32)
D
≥
500 (19-11/16)
E
≥
20 (25/32)
F
≥
1800 (70-7/8)
A
≥
50 (1-31/32)
B
≥
500 (19-11/16)
C
≥
50 (1-31/32)
D
≥
500 (19-11/16)
E
≥
100 (3-15/16)
F
≥
1200 (47-1/4)
Only 2
sides
are
walls
A
≥
10 (13/32)
B
≥
300 (11-13/16)
A
≥
10 (13/32)
B
≥
300 (11-13/16)
E
≥
20 (25/32)
50
0
(19
-11
/16
’’)
D
F
E
G
50
0
(19
-11
/16
’’)
D
H
H
F
E
G
50
0
(19
-11
/16
’’)
D
H
F
E
I
G
50
0
(19
-11
/16
’’)
D
H
F
E
I
G
50
0
(19
-11
/16
’’)
D
F
E
I
G
50
0
(19
-11
/16
’’)
D
H
F
E
I
G
50
0
(19
-11
/16
’’)
D
H
H
F
E
I
G
50
0
(19
-11
/16
’’)
D
E
50
0
(19
-11
/16
’’)
D
H
H
E
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
Front
No limit for the
height of wall
No limit for the height of wall
Front
SELECT THE BEST LOCATION
Select space for installing outdoor unit, which will meet the following
conditions:
• No direct thermal radiation from other heat sources
• No possibility of annoying neighbors due to noise of unit
• No exposition to strong wind
• With strength which bears weight of unit
• Note that drain flows out of unit when heating
• Because of the possibility of fire, do not install unit to the space
where generation, inflow, stagnation, and leakage of combustible gas
is expected.
• Avoid unit installation in a place where acidic solution and spray (sul-
fur) are often used.
• Do not use unit under any special environment where oil, steam and
sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to pre-
vent any person or animal from accessing the outdoor unit.
• If installation site is area of heavy snowfall, then the following direc-
tions should be observed.
- Make the foundation as high as possible.
- Fit a snow protection hood.
• Select installation location considering following conditions to avoid
bad condition when additionally performing defrost operation.
- Install the outdoor unit at a place well ventilated and having a lot of
sunshine in case of installing the product at a place With a high hu-
midity in winter (near beach, coast, lake, etc.)
(Ex : Rooftop where there is always sunshine.)
1,MFL67221438,영영 2018. 10. 4. 영영 11:29 Page 6