THE INDOOR UNIT INSTALLATION
ENGLISH
- Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on
the ceiling.
- Mount the suspension bolts to the set anchor firmly.
- Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, wash-
ers and spring washers.
• Local supply
①
Set anchor
②
Plate washer - M10
③
Spring washer - M10
④
Nut - W3/8 or M10
⑤
Suspension bolt - W3/8 or M10
9
1 Set anchor
Old building
New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
Tighten the nut and bolt to prevent unit falling.
CAUTION
!
1
Install declination of the indoor unit is very important for the drain of the duct type air
conditioner.
2
Minimum thickness of the insulation for the connecting pipe shall be 10mm.
CAUTION
!
Ceiling
1~3mm
Drainage hole
Drainage hole
Safety drain hole
Main drain hole
CORRECT
INCORRECT