Chapter 7 Usage of Various Functions
7-55
7.2.3 D/A Conversion module
1) Performance specifications
The performance specifications of the analog output module are following
.
Specifications
Item
G7F-DA2I
G7F-DA2V
Output Range
DC 0
∼
20
㎃
( Load resistance 510
Ω
)
DC 4
∼
20
㎃
( Load resistance 510
Ω
)
Classified by parameter
DC 0 ~ 10V(Lod resistance 2
㏀∼
1
㏁
)
Digital Output
12bit (0
∼
4000)
Number of output
4channels/1module
Max. absolute output
DC +24
㎃
DC
12V
DC 0
∼
20
㎃
: 5
㎂
(1/4000)
Maximum
resolution
DC 4
∼
20
㎃
: 6.25
㎂
(1/3200)
2.5
㎷
(1/4000)
Overall accuracy
±
0.5% [Full Scale]
Max. conversion speed
0.5
㎳
/CH + scan time
1
㎳
/CH + scan time
Isolation
Between input terminal and PLC power supply: Photo coupler isolation
(No isolation between channels)
Terminal connected
16 points terminal block
8 points terminal block * 2
Current
Consumption
20mA 15mA
Voltage
DC 21.6 ~ 26.4V
External
Power supply Current
consumption
80
㎃
90
㎃
Weight 280g
160g