background image

–31–

9. Indoor Unit Drain Piping

• Drain piping must have down-slope (1/50 to 1/100): be sure

not to provide up-and-down slope to prevent reversal flow.

• During drain piping connection, be careful not to exert extra

force on the drain port on the indoor unit.

• The outside diameter of the drain connection on the indoor

unit is 32mm.

• Be sure to install heat insulation on the drain piping.

Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings

The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:

• Connect the main drain pipe to the exterior

and leave it provisionally until the test
comes to an end.

• Feed water to the flexible drain hose and

check the piping for leakage.

• Be sure to check the drain pump for normal

operating and noise when electrical wiring
is complete.

• When the test is complete, connect the

flexible drain hose to the drain port on the
indoor unit.

Heat insulation material: Polyethylene foam with
thickness more than 8 mm.

Drain test

Maintenance
drain port

Upward
routing
not allowed

Pipe clamp

Indoor unit

1/50~1/100

MAX 700mm

Flexible drain hose

Feed water

Drain Pump

Drain pan

Flexible drain hose
(accessory)

Main 
drain pipe

Glue the joint

Drain
port

Drain hose connection
Use the clip (accessory)

Flexible drain hose

CAUTION

The supplied flexible drain hose should not be curved,
neither screwed. The curved or screwed hose may
cause a leakage of water.

1/50~1/100

MAX 700mm

Flexible drain hose

Flexible drain hose

After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the

circuit diagram pasted on the inside of control box cover.

2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the

unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they
are loose, it could give rise to burn-out of the wires.)

4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.

(Particularly note the relation between cable length and thickness.)

8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.

• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a

overload protection device.

• Proper starting power is not given to the compressor.

CAUTION

Summary of Contents for LT-C182ELE0

Page 1: ...Conditioner SERVICE MANUAL MODELS LT E1820CL LT E1820HL LT E1860CL LT E1860HL LT E1860AA LT E1862HL LT E2460CL LT E2460HL LT E2460BL LT E2462HL LT E2462CL LT E2460AA LT C182ELE0 LT H182ELE0 LT H246ELE0 ELF0 LT C246ELE0 ELF0 ...

Page 2: ...igeration Cycle Diagram 12 Wiring Diagram 14 Operation Details 17 Installation of Indoor Outdoor Unit 20 Cycle 38 Cycle Troubleshooting Guide 41 Electronic Parts Troubleshooting Guide 42 Electronic Control Device 45 Schematic Digram 46 Exploded View and Replacement Parts List 47 2 ...

Page 3: ...n motor is selected to increase air reaching distance Central Control Optional It is operating individually or totally by central control function Group Control Optional Wiring Elevation Grille Optional Each controller can control 16 units and 8 controllers can be connected It operates maximum 16 units by only one wired remote con troller and each unit starts sequentially to prevent overcurrent Au...

Page 4: ...Cooling model only Heating model only Low Med High Cooling Operation Mode Heating Operation Mode Auto Operation Mode Soft Dry Operation Mode Fan Operation Mode HI JET AUTO MED LO Program Holiday SET CLR Min Hour Week Timer Cancel Timer Cancel High 39 C LOW 11 C Fan Operates without cooling heating Cooling Heating Down to 18 C Up to 30 C Down to 16 C Up to 30 C ...

Page 5: ...Or else there is worry about trouble failure Do not press hard the Remote Controller button with nail ball point pen or other sharp substance Or else there is worry about trouble failure In case when obstacle such as curtain hides the signal reception part of receiver in between the space interval Remote Controller operation is infeasible Lift grill front panel assembly Bolts for installation 4 EA...

Page 6: ...nd enters into the front panel 1 Stop the Air Conditioner Operation 2 Descend the Suction Grill 3 Raise the Suction Grill Depress the stop button Make use of this when you want to stop it at your wished posi tion 4 Stop the Suction Grill during Rising Always stop the air conditioner operation for safety before operating lift grill Take heed _ there is worry about dust fall etc when suction grill d...

Page 7: ... 60 14 3 2 5 18 4 0 75 1 4 6 35mm 5 8 15 88mm 50 30 FoamPE 5mm ø25 32 1 220 60 4 536 5 274 18 000 4 536 5 274 18 000 1 900 1 900 8 8 8 8 53 53 2 39 2 78 13 50 1 9 O O 4 O O O O O 4 O O O O O O Optional O X 1 910 570 x 570 x 269 670 x 670 x 30 870 x 655 x 320 19 61 14 3 2 5 18 6 0 75 1 4 6 35mm 5 8 15 88mm 50 30 FoamPE 5mm ø25 32 LT E2460AA LT E1860CL LT E1860HL LT E1862HL LT E1820CL LT C182ELE0 LT...

Page 8: ...62 2 26 15 5 50 2 9 O X 4 O O O O O 4 O X O O O O Optional O X 1 900 570 x 570 x 269 670 x 670 x 30 870 x 655 x 320 19 16 5 2 5 61 14 3 2 5 18 4 0 75 1 4 6 35mm 5 8 15 88mm 50 30 FoamPE 5mm ø25 32 1 220 240 50 5 871 6 827 23 300 5 922 6 886 23 500 2 600 2 600 13 5 13 5 62 60 2 26 2 65 15 5 50 2 9 O O 4 O O O O O 4 O O O O O O Optional O X 1 900 570 x 570 x 269 670 x 670 x 30 870 x 655 x 320 19 16 ...

Page 9: ...Dimensions 9 269 670 55 570 269 190 5 160 52 90 90 120 4 30 521 670 570 450 40 110 110 670 670 CLOSE OPEN OPEN CLOSE 1 Indoor Unit ...

Page 10: ... 10 LT H ELE0 LT H FLE0 LT H DLE0 W D H W mm 670 850 950 H mm 90 90 90 D mm 670 850 950 unit mm Model LT H ELE0 LT H FLE0 LT H DLE0 DIM Unit ...

Page 11: ... way valve Liquid side 3 way valve W L6 L7 L8 L9 L4 L11 L10 D L1 L2 L5 L3 MODEL DIM W mm 870 H mm 655 D mm 320 L1 mm 370 L2 mm 25 L3 mm 340 L4 mm 630 L5 mm 25 L6 mm 546 L7 mm 162 L8 mm 162 L9 mm 54 L10 mm 74 5 L11 mm 79 All Models ...

Page 12: ...nt should be added 15 7 5 x25g 12 INDOOR UNIT H EX Liquid Side Liquid Side Gas Side COMPRESSOR VALVE REVERSING ACCUM H EX Gas Side Gas Side Liquid Side CAPI C1 CAPI A CAPI B Heating Cooring CAPI C2 OUTDOOR UNIT GAS LIQUID Elevation m Length m Additional refrigerant g m Pipe Size Rated Rated Max Max Capacity 18K 5 8 1 4 7 5 50 5 30 25 24K 5 8 1 4 7 5 50 5 30 30 ...

Page 13: ...frigerant should be added 15 7 5 x25g INDOOR UNIT H EX Liquid Side Liquid Side Liquid Side COMPRESSOR ACCUM H EX Gas Side Gas Side Gas Side CAPI C1 CAPI A CAPI B CAPI C2 OUTDOOR UNIT GAS LIQUID Elevation m Length m Additional refrigerant g m Pipe Size Rated Rated Max Max Capacity 18K 5 8 1 4 7 5 50 5 30 25 24K 5 8 1 4 7 5 50 5 30 30 ...

Page 14: ... 7 8 INDOOR MOTOR DRAIN PUMP STEP MOTOR TEMP THERMISTOR PIPE THERMISTOR REMOTE CONTROL FLOAT S W CN DISP DISPLAY PCB Only for LT Exxx2HL AIR CLEANER H V ASSY DOOR S W TERMINAL BLOCK TO OUTDOOR UNIT BR YL BK OR BL BL BR GN YL RD BK YL BL GN YL OUT FAN COMP 4 WAY RD BK WH RD BK 3 L 4 N 5 6 7 FUSE T3 15A OUTDOOR WIRING DIAGRAM COMP R S H 4 2 8 6 1 0 C F BL YL YL WH YL OR BK TB2 BR BR BR BR BL BL BL B...

Page 15: ... RD CAPACITOR RD C POWER RELAY FAN MOTOR FUSE 5A FUSE 5A POWER INPUT TO INDOOR UNIT TERMINAL BLOCK 1 L 2 N 3 L 4 N 5 6 7 8 OUTDOOR WIRING DIAGRAM INDOOR WIRING DIAGRAM INDOOR MOTOR DRAIN PUMP STEP MOTOR TEMP THERMISTOR PIPE THERMISTOR REMOTE CONTROL FLOAT S W CN DISP DISPLAY PCB LT E 2HL ONLY AIR CLEANER H V ASSY DOOR S W TERMINAL BLOCK TO OUTDOOR UNIT BR YL BK OR BL BL BR GN YL RD YL BL GN YL COM...

Page 16: ... 16 ELEVATION GRILL WIRING DIAGRAM INDOOR LT H DLE0 LT C DLE0 LT H ELE0 LT C ELE0 LT H FLE0 LT C FLE0 ...

Page 17: ...and down automatically 3 Air Filter Checking Control Filter will display in the remote controller display and main body display when an air filter is polluted Then clean the air filter for reference to Owners Manual 4 Soft Dry Operation The indoor fan speed is automatically set to the low so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Oper...

Page 18: ...operates at low speed 6 Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as follows Hot Start Low OFF Selected Fan Speed minimum 3min Selecting fan speed Low Low Low OFF OFF minimum 10sec 1min A A minimum 1min minimum 10sec B 7 Hot Start Control The indoor fan stops until the evaporator piping temperature reaches to 2...

Page 19: ... between the indoor pipe temperatures of 25 min later TE1 and 45 min later TE2 after heating mode operation started When the indoor pipe temp is 41 C or above defrost control is not carried out even if the condition is one of the defrost conditions above While in defrost control the compressor is on and the indoor fan the outdoor fan and the 4 way valve are off 9 Self diagnosis Function CHECK will...

Page 20: ...that heat radiation from the condenser is not restricted There should not be any animals or plants which could be affected by hot air discharged Ensure the spaces indicated by arrows from the wall ceiling fence or other obstacles 3 Piping length and the elevation More than 30cm Sunroof Fence or obstacles More than 70cm More than 50cm More than More than 30cm More than 30cm Indoor unit Outdoor unit...

Page 21: ...erated 5 Avoid places near high frequency generators 2 Ceiling opening dimensions and hanging bolt location Unit mm 570 Unit size 570 Unit size 450 Hanging bolt 75 75 600 Ceiling opening 600 Ceiling opening 521 Hanging bolt 39 5 39 5 Ceiling board Level gauge Ceiling Use the ventilation fan for smoke collecting hood with sufficient capacity Cooking table Air conditioner Take enough distance The di...

Page 22: ...ller Installation Although the room temperature sensor is in the indoor unit the remote controller should be installed in such places away from direct sunlight and high humidity Installation of the remote controller Select places that are not splashed with water Select control position after discussion with customer The room temperature sensor is built in the indoor unit This remote controller is ...

Page 23: ...ure that both batteries are new Re attach the cover Slide it back into position WIRED REMOTE CONTROL INSTALLATION REMOTE CONTROL PREPARATION OPTIONAL DISASSEMBLING ELECTRICAL WIRING HOW TO MOUNT ON A WALL HOW TO INSERT BATTERIES Make sure that wire and teminal numbers are matched on unit side and remote controller side The maximum length of the cord is 100m If the length of the cord exceeds 50m us...

Page 24: ...inal Block of Indoor Unit 3 L 4 N 5 6 7 1 L 2 N 3 L 4 N 5 6 7 8 Terminal Block of Outdoor Unit Power Cord Terminal Block of Indoor Unit 3 L 4 N 5 6 7 1 L 2 N 3 L 4 N 5 6 7 8 Terminal Block of Outdoor Unit Power Cord Control box cover Indoor power cord Remote controller cord Control box cover fitting screw 2 units 5 Wiring Connection Open the control box cover and connect the Remote controller cord...

Page 25: ...CAL REGULATION Main power source Switch box Refrigerant pipe Circuit Breaker Use circuit breaker or time delay fuse ELECTRICAL WIRING CONNECTING THE CABLE TO OUTDOOR UNIT 1 Remove the Cover control from the unit by loosening a screw Connect the wires to the terminals on the control board individually as following 2 Secure the cable onto the control board with the hold er clamper 3 Refix the cover ...

Page 26: ...s a little longer than measured distance Cut the cable 1 5m longer than the pipe length 2 Burrs removal Completely remove all burrs from the cut cross section of pipe tube Put the end of the copper tube pipe to downward direc tion as you remove burrs in order to avoid to let burrs drop in the tubing 3 Putting nut on Remove flare nuts attached to indoor and outdoor units than put them on pipe tube ...

Page 27: ...re to check if there is gas leakage in indoor and outdoor connection After completing the piping connection execute vacuum drying for the connecting piping and the indoor unit The vacuum drying must be carried out using the ser vice ports of both the liquid and gas side valves Use two wrenches and tighten with regular torque Outdoor unit Liquid side Flare connection Flare connection Gas side Indoo...

Page 28: ...tall the air inlet grille including the air filter Decoration panel fixing screws hexagon M5 screws Temporally fitting at 2 places Tightening about 10mm Control box cover Piping side Inlet Grille Inlet Grille Inlet Grille Inlet Grille Inlet Grille Louver motor Decoration panel fixing screws Hexagon M5 screw Air conditioner unit Decoration panel Key holes Display Lead wire for louver motor and disp...

Page 29: ... hexagon M5 screw are included unit box 2 Remove the air inlet grille from the decoration panel Remove the hook for the air inlet grille cord 3 Hook the decoration panel key hole on the screws fixed in step above and slide the panel so that the screws reach the key hole edge 4 Retighten completely two temporarily fixed screws and other two screws Total 4 screws 5 Connect the louver motor connector...

Page 30: ...l Don t draw out suction grill irrationally Or else there is worry that lift grill drive part is damaged and suction grill might drop down Don t place obstacle in lift passage of lift grill When suction grill descends it automatically stops at a certain distance If there is any obstacle in lift passage suction grill might drop down and there may be caused trouble failure of lift grill drive part T...

Page 31: ...supplied flexible drain hose should not be curved neither screwed The curved or screwed hose may cause a leakage of water 1 50 1 100 MAX 700mm Flexible drain hose Flexible drain hose After the confirmation of the above conditions prepare the wiring as follows 1 Never fail to have an individual power specialized for the air conditioner As for the method of wiring be guided by the circuit diagram pa...

Page 32: ...ck pip ing and drain piping add further 10mm to 30mm thickness material Indoor unit Thermal insulator accessory Fastening band accessory Refrigerant piping HEAT INSULATION 1 Wrap the connecting portion of indoor unit with the Insulation material and secure it with two Plastic Bands for the right pipings If you want to connect an additional drain hose the end of the drain outlet should keep distanc...

Page 33: ...18 minutes later automatically The test run is started by pressing the room temperature checking button and down timer button for 3 sec onds at the same time To cancel the test run press any button After completing work be sure to measure and record trial run properties and store measured data etc Measuring data are room temperature outside temperature suction temperature blow out temperature air ...

Page 34: ...aker switch between power source and the unit 3 The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could give rise to burn out of the wires 4 Specification of power source 5 Confirm that elec...

Page 35: ...main body and of remote controller sensor 3 Move the slide switch to set position 4 Close the rear cover and check if it works normally TH R14H SW TH REMO MAIN 2TH OP7 R18H R17H OP6 LO STAND SW HIGH HI R03S C070 R04S R02S R01S OP3 OP2 OP1 R19H R11H R13H R12H OP5R16H OP4 R15H CO1H REMO Room Temp sensor 2TH MAIN Position 2 Position 1 Position 3 Slide switch for ceiling height Slide switch for 2Therm...

Page 36: ...TAND Slide switch for ceiling height Slide switch for 2Thermistor Standard Default Low ceiling High Ceiling Ceiling height Mode of slide switch Change of air volume Remark more than 3 3m High Ceiling Increasing 2 7 3 3m Standard less than 2 7m Low Ceiling Decreasing Maunfactured in stan dard mode NOTICE NOTICE OUTDOOR WIRING DIAGRAM INDOOR WIRING DIAGRAM COMP R S H 4 2 8 6 1 0 C F BL YL OR BK TB2 ...

Page 37: ...perates maximum 16 Units by only one Wired Remote Controller and each Unit starts sequentially to prevent overcurrent Operation unit ZONE 1 2 3 4 Humidify JET AUTO AUTO SWING OPERATION FAN SPEED Program set SUB FUNCTION SET TEMP Room Temp HI MED LO Heater Defrost Filter Preheat Out door Time Timer On Set no Time Off 01 03 05 07 09 11 13 15 17 19 21 23 Indoor Unit 1 Terminal Local Supply Block Term...

Page 38: ...f there is no leakage discharge N2 in piping com pletely into tank for retrieving Completely discharge is needed for vacuuming If leakage is found please fasten the joint more tight ly 6 After closing the valve of charging hose discon nect the tank and connect the vacuum pump to charging hose and open the valve again for vacu uming 7 Turn on the vacuum pump until the pressure drops below 0 kg cm2 ...

Page 39: ... and then close it tightly 3 Operate the air conditioner for 10 15 min until cycle is stabilized 4 Close the spindle of service port liquid side high pressure and wait till pressure of gas side low pressure drops below 0 kgf cm2 5 After the needle of gage indicates below 0 kgf cm2 close the valve of gas side quickly and turn off the power 6 Disconnect the piping between indoor and outdoor unit and...

Page 40: ... approximately 150g each time while operating the air conditioner in the cooling cycle however one time is not suffi cient wait approximately 1 minute and then repeat the procedure 4 Immediately disconnect the charge hose from the 3 way valve s service port Stopping partway will allow the gas to be dis charged If the system has been charged with liquid refrigerant while operating the air condition...

Page 41: ...room air humidity When the room air humidity is relativery higher temperature difference is smaller When the room air humidity is relatively lower tem perature difference is larger 2 Check temperature and pressure of refrigeration cycle Notice 1 The suction pressure is usually 4 5 6 0 kg cm2 G at normal condition 2 The temperature can be measured by attaching the thermometer to the low pressure tu...

Page 42: ...YES NO YES Is the input voltage AC230V Check the FUSE and the wiring diagram Is the PIN 49 58 of MICOM DC5V Exchange MICOM YES NO Check the main P C B pattern NO YES Is the output voltage of IC03D DC5V NO Exchange IC03D Is the input voltage of IC03D about DC12V Check the 5V P C B pattern ...

Page 43: ...s the each Relay any problem YES NO YES It is normal operation Exchange IC01M Exchange Relay YES YES NO YES Is it Heating Mode Does the temperature set all right Change IC01M NO NO Adjust operation mode Adjust set temperature Is IC01M operated normally YES Check the connector CN OUT Check RY 4Way NO Is 4way valve operated Possible Trouble 3 Ineffective Heating ...

Page 44: ...d normally Check the motor and connector CN LOUVER Exchange IC01M NO YES YES YES Is the LCD operated normally Is the terminal of wired Remocon T2 DC12V Is the pin 39 40 of Micom DC 5V Change the wired Remocon Check the wired Remocon PCB and DC 12V pattern NO NO Check the parts of communication Connector CN Remo and terminals of wired Remocon exactly ...

Page 45: ... 45 Electronic control device MAIN P C B ASM ...

Page 46: ...F INR14D561K ZNR01J T3 15A 3A 250V 22mH 3A 1 2 NF01J P6KE200A ZD01D DC310V NTC01D 400V 10uF C01D 10D 9 AC_N 1N4007 R01J D01D D03D C03D UF4005 TNY255P IC01D 4 1 S 2 255P TNY 5 D02D D 3 EN BP 4 5 UF5402 S Trans 1 6 7 36 33 35 34 39 38 37 41 40 44 43 42 46 45 CN ROOM CN PIPE ZD02D 57 52 47 49 48 51 50 54 53 56 55 60 59 58 62 61 11V 63 64 STEP M KID65004AF IC02M DC 12V 1 1 3 3 C08D 104 3 3uH R03D R04D...

Page 47: ...Exploded View and Replacement Parts List 1 Indoor Unit 47 354212 249951 266090 268714 266012 35211A 263230 352118 330870 158591 159830 ...

Page 48: ... 48 346810 130411 359011 152302 135802 135312 2 W0CZZ 135312 1 267110 267110 352150 352150 130911 140570 268712 146811 ...

Page 49: ... 49 137211 W4811 2 146812 2 146812 1 W4811 1 435310 152312 268712 668713 249951 146811 146811 267110 750830 266011 2 266011 2 Elevation Grille ...

Page 50: ...C 4681AC2026D 4681AC2026D R 359011 FAN TURBO 5900A10004A 5900A10004A 5900A10004A 5900A10004A R 130911 CABINET ASSY INDOOR 3091A10023C D 3091A10023C D 3091A10023C D 3091A10023C D R 135312 1 PANEL ASSY FRONT INDOOR 3721A10021A 3721A10021B 3721A10021A 3721A10021A R 146811 MOTOR ASSY STEP 4681AP2968D 4681AP2968D 4681AP2968D 4681AP2968D R 268712 PWB PCB ASSY DISPLAY 6871A20096C 6871A20096C 6871A20096C ...

Page 51: ...A 4056A20001A R 130911 CABINET ASSY INDOOR 3091A10023C D 3091A10023C D 3091A10023C D 3091A10023C D R 352150 DRAIN ASSY TUBE 5251A20002A 5251A20002A R 135312 1 PANEL ASSY FRONT INDOOR 3721A10021B 3721A10021B 3721A10105A 3721A10105B R 146811 MOTOR ASSY STEP 4681AP2968D 4681AP2968D 4681A20055A 4681A20055A R 268712 PWB PCB ASSY DISPLAY 6871A20096C 6871A20096C 6871A20096J 6871A20096J R 152302 FILTER AS...

Page 52: ...4056A20001A 4056A20001A 4056A20001A R 130911 CABINET ASSY INDOOR 3091A10023A B 3091A10023C D 3091A10023C D 3091A10023A B R 352150 DRAIN ASSY TUBE 5251A20002A 5251A20002A 5251A20002A 5251A20002A R 135312 1 PANEL ASSY FRONT INDOOR 3721A10021C 3721A10021S 3721A10021C 3721A10021C R 146811 MOTOR ASSY STEP 4681AP2968D 4681AP2968D 4681AP2968D 4681AP2968D R 268712 PWB PCB ASSY DISPLAY 6871A20096A 6871A200...

Page 53: ...01A 4056A20001A 4056A20001A 4056A20001A R 130911 CABINET ASSY INDOOR 3091A10023C D 3091A10023C D 3091A10023B 3091A10023C D R 352150 DRAIN ASSY TUBE 5251A20002A 5251A20002A 5251A20002A 5251A20002A R 135312 1 PANEL ASSY FRONT INDOOR 3721A10105C 3721A10105A 3721A10021S 3721A10105C R 146811 MOTOR ASSY STEP 4681A20055A 4681A20055A 4681AP2968D 4681A20055A R 268712 PWB PCB ASSY DISPLAY 6871A20096J 6871A2...

Page 54: ...14001T R 263230 THERMISTOR ASSEMBLY 6323AQ3226F R 266001 SWITCH MICRO 2H01323A R 266012 SWITCH ASSEMBLY FLOAT 6601A20001G R 266090 H V ASSEMBLY 6609A20005C R 267110 REMOTE CONTROLLER ASSEMBLY 6711A20076K R 268712 PWB PCB ASSEMBLY DISPLAY 6871A20096J R 268714 PWB PCB ASSEMBLY MAIN 6871A10338Y R 330870 DRAIN PAN ASSEMBLY 3087A10002A R 346810 MOTOR ASSEMBLY SINGLE 4681AC2026D R 352118 TUBE ASSEMBLY M...

Page 55: ...SSEMBLY MICRO 6601A20002D 6601A20002D 6601A20002C R 266011 2 SWITCH ASSEMBLY MICRO 6601A20002E 6601A20002E R 146812 1 MOTOR ASSEMBLY SYNC 4681AP2596J 4681AP2596J 4681AP2596H R 146812 2 MOTOR ASSEMBLY SYNC 4681AP2596M 4681AP2596M R 750830 ROPE ASSEMBLY 5083A20002A 5083A20002A 5083A20002A R 249951 CONTROL BOX ASSEMBLY INDOOR 4995A20450B 4995A20450A 4995A20450A R 668713 PWB PCB ASSEMBLY SUB 6871A2036...

Page 56: ... 56 2 Outdoor Unit 435512 546810 549610 554031 554160 552203 1 649950 435511 669200 552202 561410 W0CZZ 1 552203 2 447910 550140 559010 430410 135301 349480 437212 437210 268717 W0CZZ 2 ...

Page 57: ...VIDE P15 88 2A00392E 2A00392E 2A00392E 2A90028E 2A00392E 2A00392E R 552203 2 VALVE SERVICE P6 35 2H02479B 2H02479F 2H02479F 2H02479B 2H02479F 2H02479F R 554031 CONDENSER ASSY BENT 5402AR2347K 5403A20006Y 5402AR2347K 5402AR2347H 5402AR2347K 5403A20006Y R 554160 COMPRESSOR ASSY FINAL 5416A20016A 5416A20016A 2A00713D 2520UMBK2PA 2A00713D 2A00713D R 559010 FAN ASSY PROPELLER 1A00195B 1A00195B 1A00195B...

Page 58: ...DOOR 2H02110M R 546810 MOTOR ASSEMBLY OUTDOOR 4681A20013K R 549610 MOUNT MOTOR 4960AP1361A R 550140 ISOLATOR COMP 4H01765A R 552113 TUBE ASSEMBLY CAPILLARY 5211A20252F R 552203 1 VALVE SERVICE 2A00392E R 552203 2 VALVE SERVICE 2H02479F R 554031 CONDENSER ASSEMBLY BENT 5403A20006Y R 554160 COMPRESSOR ASSEMBLY 2A00713D R 559010 FAN ASSEMBLY PROPELLER 1A00195B R 649950 CONTROL BOX ASSEMBLY OUTDOOR 49...

Page 59: ...2347B 5403A20051D 5402AR2347B 5402AR2347B 554160 COMPRESSOR ASSY FINAL 5416A20016A 5416A20016A 2A00713D 2A00713D 2A00713D R 5416A20016E 5416A20016E 559010 FAN ASSY PROPELLER 1A00195B 1A00195B 1A00195B 1A00195B 1A00195B 1A00195B 1A00195B R 4995A20014C 4995A20014C 4995A20014C 4995A20014C 4995A20014C 649950 CONTROL BOX ASSY OUTDOOR 4995A20014W 4995A20014W OnlyAustralia W0CZZ 1 CAPACITOR DRAWING 6120A...

Page 60: ...P No 3828A20048D August 2005 Printed in Korea ...

Reviews: