2. Faults
2-1. Power
2-2. Compressor
Problems
Causes
Checks
Measures
Remarks
No power on
- Power cord cut.
- Check the voltage with tester.
-Replace the components.
outlet.
- Faulty connector insertion.
- Check visually.
-Reconnect the connecting parts.
- Faulty connection between plug
- Check visually.
-Reconnect the connecting parts.
and adapter.
Fuse blows out. - Short circuit by wrong connection.
- Check the fuse with tester
- Find and remove the cause of
- Replace with rated
- Low voltage products are
or visually.
problem (ex. short, high voltage,
fuse after confirming
connected to high voltage.
- Check the input volt are with tester
low voltage).
its specification.
- Short circuit by insects.
(between power cord and products). - Replace with rated fuse.
- Electricity leakage.
- Check the resistance of power cord
If fuse blowns out
- High voltage.
with tester (if it is 0 , it is shorted).
frequently, confirm
- Short circuit of components
the cause and prevent.
(tracking due to moisture and dust
penetration).
Problems
Causes
Checks
Measures
Remarks
Compressor
- Faulty Combo.
- Check the resistance.
- If resistance is infinite, replace it
does not
Vlaue:
is defective.
with new one.
operate.
- If it is not infinite, it is normal.
- Check other parts.
- Compressor is frozen.
- If compressor assembly parts are
- During forced operation:
normal (capacitor, PTC, OLP),
- Operates: Check other parts.
apply power directly to the
- Not operate: Replace the frozen
compressor to force operation.
compressor with new one, weld,
evacuate, and recharge refrigerant.
OLP It starts as soon as it is
• Refer to weld repair procedures.
contacted.
Auxiliary winding
Main winding
Power
- 51 -