16
6LQJOH=RQH+LJK(ႈFLHQF\6WDQGDUG:
DOO0RXQW,QVWDOODWLRQ0DQX
DO
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
GENERAL INSTALLATION GUIDELINES
Rigging and Lifting / Outdoor Unit Mounting
Rigging and Lifting Instructions
Wear protective gloves and safety goggles when handling equipment. Sharp edges will cause personal injury.
Dispose of the packing materials safely.
• Packing materials, such as nails and other metal or wooden parts, will cause puncture wounds or other injuries.
• Tear apart and throw away plastic packaging bags so that children do not play with them and risk suffocation and death.
• Be very careful when transporting the product. There is a risk of the product falling and causing physical injury.
• Use appropriate moving equipment to transport each frame; ensure the equipment is capable of supporting the weights listed.
• Some products use polypropylene bands for packaging.
Do not use polypropylene bands to lift the unit.
• Support the outdoor unit at a minimum of four points to avoid slippage from rigging apparatus.
• Make sure the outdoor unit is in its original packaging to avoid damage during local transport.
• At the time of delivery, the package must be checked for any damage (exterior and interior). Report any damage to the carrier claims agent
immediately.
• Handle the outdoor unit with care. Keep the outdoor unit upright to avoid damaging inside components.
• If a forklift is to transport the outdoor unit, the forklift arms must pass through the openings at the bottom.
• If a crane is to suspend the outdoor unit, it is required that two (2) ropes at least twenty-three (23) feet in length be used. Pass the ropes under
the unit. Pass the rope through the two (2) forklift slots each at the front and rear of the outdoor unit.
•
7RSUHYHQWGDPDJHWRWKHRXWGRRUXQLWDOZD\VOLIWWKHXQLWZLWKWKHURSHVDWWDFKHGDWIRXUSRLQWVDWDQDQJOHRI
• Always include padding to protect the outdoor unit from rope damage, and take into consideration the outdoor unit’s center of gravity.
General Outdoor Unit Mounting
Any underlying structure or foundation must be designed to support
the weight of the outdoor unit.
Avoid placing the unit in a low
lying area where water and ice will accumulate. Securely attach the
outdoor unit to a condenser pad, base rails, or a mounting platform
that is solidly anchored to the ground or building structure. When
installing the outdoor unit on the wall or roof top, securely anchor the
mounting base to account for wind, earthquakes, or vibration.
Anchoring the Outdoor Unit
• Tightly anchor the outdoor unit with a bolt and nut to a concrete or
rigid platform (see next page for more details).
• When installing on a wall (with field-supplied brackets), roof, or
rooftop, securely anchor the mounting platform with nails, taking
into consideration the possibility of strong winds or earthquakes.
• If there is a possibility of vibration from the outdoor unit transmit-
ting to the building, add an anti-vibration material.
Follow applicable local codes for clearance, mounting, anchor and vibration attenuation requirements.
Figure 5: Examples of Outdoor Unit Mounting Methods.