GENERAL DATA
Table 2: Single Zone High Ef
¿
ciency Standard Wall Mount System Electrical Data.
Electrical
Nominal
Tons
Unit Model
No.
Hertz Voltage
Voltage
Range
(Min. to Max.)
MCA MOP Compressor
Quantity
Compressor Motor
RLA
Outdoor Fan Motor
Indoor
Fan
Motor
Cooling Heating
kW
FLA
FLA
3/4
LS090HSV5
60
208 - 230
187 - 253
10.0
15.0
1
7.0
7.0
0.043
0.4
0.4
1
LS120HSV5
10.0
15.0
1
7.0
7.0
0.043
0.4
0.4
1-1/2
LS180HSV5
13.0
20.0
1
9.6
9.6
0.124
0.25
0.4
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded
down to the nearest standard fuse size.
RLA = Rated Load Amps.
FLA = Full Load Amps.