- 37 -
1) Connect the cable to the Indoor unit.
Connect the cable to the indoor unit by connect-
ing the wires to the terminals on the control
board individually according to the outdoor unit
connection.
(Ensure that the color of the wires of the outdoor
unit and the terminal No. are the same as those
of the indoor unit.)
CAUTION
The power cord connected to the indoor unit should
be complied with the following specifications
(Type H05VV-F approved by HAR or SAA).
1(L)
Terminals on the outdoor unit
Terminals on the indoor unit
1(L)
2(N)
2(N)
BROWN
BLUE GREEN/YELLOW
BROWN
BLUE GREEN/YELLOW
Terminals on the outdoor unit
Terminals on the indoor unit
1(L)
1(L)
2(N)
2(N)
3
4
3
4
BROWN BLUE
G/Y
BLACK
RED
BROWN BLUE
G/Y
RED
BROWN BLUE
BLACK
BLACK
G/Y
RED
RED
G/Y
BLUE
BROWN
The power connecting cable connected to the indoor
and outdoor unit should be complied with the following
specifications
(Type H07RN-F approved by HAR or SAA).
The connecting cable connected to the indoor and
outdoor unit should be complied with the following
specifications
(Type H07RN-F approved by HAR or SAA).
• Cooling model
• Heat pump model
Color of Wires
Color of Wires
Color of Wires
Color of Wires
The length of the power supply cord should be over 1.8m
measured from the power supply cord entry of the cabinet
to the middle of the live pin of the plug.
Air
Conditioner
Main power source
If a power plug is not to be used, provide a circuit breaker between power source and
the unit as shown below.
Circuit Breaker
Use a circuit break-
er or time delay
fuse.
CAUTION
Capacity
(Btu/h)
NORMAL CROSS
-SECTIONAL AREA
18K
24K
26K
1.5mm
2
2.5mm
2
Capacity
(Btu/h)
NORMAL CROSS
-SECTIONAL AREA
18K
24K
26K
1.5mm
2
2.5mm
2
3. Connecting the Cable Between Indoor Unit and Outdoor Unit
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2