-16-
■
Auto Operation for Soft Dry
The Setting temperature will be same that of auto operation for Cooling.
- Compressor ON temperature; Setting tempe0.5°C
- Compressor OFF temperature; Setting temperature -0.5°C
■
Auto Operation for Heating
Intake Air temp.
below 20°C
Over 20°C~below 21°C
Setting temp.
20°C
Intake air tempe0.5°C
7. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as fol-
lowing.
Intake Air temp.
INDOOR FAN SPEED
OFF
Hot
Start
Selecting
fan speed
Selecting
fan speed
LOW
LOW
A
minimum
10sec.
1 min.
minimum
10sec.
minimum
10sec.
A
B
LOW
OFF
LOW
OFF
COMPRESSOR
ON
OFF
ON
OFF
Setting temp. +3
°
C
(Compressor OFF)
• A point; The indoor pipe temperature to be 35
°
C.
The indoor fan operates minimum 10sec. even if falls lower than 35
°
C.
• B point; The indoor fan operates minimum 10sec.
Setting temp.
(Compressor ON)