4. Soft Dry Operation Mode
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 0.5°C, the com-
pressor OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to
the Cooling operation.
• When the room temperature falls the compressor OFF temperature, the operation mode is switched to the
Soft Dry Operation.
• The operation diagram is shown below.
-14-
INDOOR FAN
Selecting
fan speed
LOW
LOW
LOW
ON
ON
ON
OFF
OFF
OFF
LOW
OFF
Operation
Cooling
Dry Operation
COMPRESSOR
SETTING TEMP.+0.5
°
C
(COMP. ON)
ROOM TEMP.
SETTING TEMP.
(COMP. OFF)
3.2 minutes
10 minutes
40 seconds
40 seconds
3.2 minutes
maximum
10 minutes
maximum
3 minutes
5. Cooling Mode with Sleep Mode Auto Control
• When selecting the Cooling(
) combined with the Sleep Mode Auto Control( ), the operation diagram is
as following.
• The setting temperature will be automatically raised by 1°C 30 minutes later and by 2°C 1 hour later.
• The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
INTAKE AIR TEMP.
INDOOR FAN SPEED
Low
Low
Low
Low
ON
OFF
ON
Low
More than
3 minutes
More than
3 minutes
30 minutes
30 minutes
ON
OFF
COMPRESSOR
SETTING TEMP.+0.5
°
C
(Compressor ON)
SETTING TEMP.-0.5
°
C
(Compressor OFF)
1
°
C
1
°
C