5. Auto Operation
• The operation procedure is as following.
❋
If initial mode is decided, that mode is continued despite of the room temperature changing.
• Auto Operation for Cooling
- 15 -
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation mode
Indoor fan speed
are automatically decided by Fuzzy rule.
Setting temperature
Intake-air
temperature
Operation Mode
Over
below
21°C
24°C
Soft Dry
below 21°C
Heating
Over 24°C
Cooling
~
Intake-Air temp.
Setting Temp. +0.5°C
(Compressor OFF)
Setting Temp. -0.5°C
(Compressor ON)
COMPRESSOR
ON
OFF
ON
OFF
INDOOR FAN SPEED
Fuzzy Speed
Intake-air Temperature
Setting Temperature
Over 26°C
25°C
Over 24°C~below 26°C
Intake air -1°C
Over 22°C~below 24°C
Intake air -0.5°C
Over 20°C~below 22°C
Intake air temperature
below 20°C
20°C
Over 20°C~below 30°C
Fuzzy control
below 20°C
20°C
over 30°C
30°C
Operation Condition
When Auto Operation
initial start
Controlled by
Fuzzy logic
1/f rhythm
Fan Speed
Air DirectionControl
When Switch to Auto
Operation