• Rated performance for refrigerant line length of: 7.5m
NOTE:
• Thoroughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the
turbo fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduction,
spraying, dispersing of water drops, drain pump malfunction, etc.
In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient
capacity so that it draws oily steam which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air conditioner in such a place where it
may not suck in oily steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in sus-
pension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
3) Piping length and the elevation
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table
Air conditioner
Take enough
distance
MODEL
GAS
LIQUID
Cooling Model 5/8"
3/8"
7.5
30
5
15
50
Heat pump Model 5/8"
3/8"
7.5
50
5
30
70
Elevation B(m)
Length A(m)
* Additional
refrigerant
(g/m)
Pipe Size
Rated
Rated
Max.
Max.
Summary of Contents for LM-4462C2T
Page 1: ...SERVICE MANUAL Ceiling Cassette Multi Air Conditioner MODELS LM 4462H2T LM 4462C2T ...
Page 38: ... 38 Electronic control device MAIN P C B ASM ...
Page 39: ... 39 2 MAIN P C B ASM OUTDOOR ...
Page 42: ... 42 ...
Page 50: ...Memo 50 ...
Page 51: ...P No 3828A20197A January 2002 Printed in Korea ...