2

Table 1 Accessory Heaters Electrical Data

Ton

3RT

4/5RT

6.25/7.5RT

8.5/10/12.5

RT

15/17.5RT

20/25RT

Heater

Model No.

LKAEH052
LKAEH102
LKAEH052
LKAEH102
LKAEH152
LKAEH09B
LKAEH18B
LKAEH09B
LKAEH18B
LKAEH18B
LKAEH36B

LKAEH36BL

Heater

KW Rating

3.6/5.0

7.2/10.0

3.6/5.0

7.2/10.0

14.4/15.0

7.8/9.0

15.6/18.0

7.8/9.0

15.6/18.0
15.6/18.0
31.2/36.0

31.2/36.0

Control

Stages

1
1
1
1
1
1
1
1
1
1
2

2

27.6/32.2

47.4/55

29.6/34.2
49.4/57.0
69.0/79.7
30.4/35.1
50.9/58.7
35.7/41.2
56.2/64.8

56.2/64.8

97.1/112.1

97.1/112.1

60/60
60/60
60/60
60/60
90/90
60/60
70/70
60/60
70/70
70/70

125/125

125/125

60/60
60/60
60/60
60/60
90/90
60/60
70/70
60/60
70/70
70/70

125/125

125/125

-
-
-
-
-

33.0/38.1
53.3/61.5
42.0/48.4
62.4/72.0
62.4/72.0
103.4/119.3

103.4/119.3

-
-
-
-
-

60/60
70/70
60/60
80/80
80/80

125/125

125/125

-
-
-
-
-

60/60
70/70
60/60
80/80
80/80

125/125

125/125

Heater

Rated Volts

208-240/60/1
208-240/60/1
208-240/60/1
208-240/60/1
208-240/60/1
208-240/60/3
208-240/60/3
208-240/60/3
208-240/60/3
208-240/60/3
208-240/60/3

208-240/60/3

Standard indoor fan motor

M.C.A

M.C.A

M.F.S

M.F.S

M.C.B

M.C.B

Over size indoor motor

Note;

Heater KW ratings are at 208/240V for 220V unit.
M.C.A; Minimum Circuit Ampere
M.F.S; Maximum Fuse Size
M.C.B; Maximum Circuit Breaker
* HACR type Circuit Breaker per NEC.

Installation

1. Loosen the screw that secures heater

compartment access panel. Lift up, pull
towards you and slide it down to remove.

2. Remove four(4) screws from block off panel

to expose heater cavity and heaterʼs back
support bracket. Save screws for installing
heater later.(See Figure 2.)

Heater Access Panel

Compressor Access Panel

Figure 1

Figure 2

: Open and lock unit disconnect

switch before installing this accessory to prevent
injury or death due to electrical shock or contact
with moving parts.

WARNING

Support

Bracket

Block off panel

Heater Cavity

Summary of Contents for LKAEH052

Page 1: ...2 LKAEH102 LKAEH152 LKAEH09B LKAEH18B LKAEH36B LKAEH36BL Please read this instruction sheet completely before installing the product Installation work must be performed in accordance with national wiring standards by authorized personnel only P No 3828A30038B ...

Page 2: ... 80 80 80 125 125 125 125 Heater Rated Volts 208 240 60 1 208 240 60 1 208 240 60 1 208 240 60 1 208 240 60 1 208 240 60 3 208 240 60 3 208 240 60 3 208 240 60 3 208 240 60 3 208 240 60 3 208 240 60 3 Standard indoor fan motor M C A M C A M F S M F S M C B M C B Over size indoor motor Note Heater KW ratings are at 208 240V for 220V unit M C A Minimum Circuit Ampere M F S Maximum Fuse Size M C B Ma...

Page 3: ...ure the heater control assembly of heater cavity using four 4 screws See Figure 4 Important Make sure the heater arm slides into heaterʼs back support bracket Two Bank Heaters Installation LKAEH36B 7 For two heaters installation align holes and secure screws to the control box as shown in Figure 3 8 Secure the heater control assembly on heater cavity using four 4 screws See Figure 5 Important Make...

Page 4: ...th heater 13 Check to make certain the proper size fuses are installed per the fuse table for the exact heater being used 14 Ground unit at the grounding lug provided Make sure all field wiring complies with all applicable codes and water tightness Figure 7 15 Remove compressor panel then remove unitʼs control box cover Connect high voltage leads to bottom of compressor contactor or terminal block...

Reviews: