Electrical Requirements
— 16 —
Table-18
Electrical Data Unit wiring
5
LK-0580HC
342~456
12.5
25
25
-
-
-
LK-0580CC
12.5
25
25
-
-
-
7.5
LK-0880HH
342~456
20
25
25
23
25
25
LK-0880CH
20
25
25
23
25
25
10
LK-1080HH
342~456
27
35
35
-
-
-
LK-1080CH
30
35
35
-
-
-
15
LK-1580HH
342-456
40.6
60
60
43
60
60
LK-1580CH
41.9
60
60
45
60
60
20
LK-2080CH
342-456
53.8
70
70
62
80
80
Tons
MODEL
Unit Operating
Voltage Range
Standard indoor fan motor
Oversized indoor fan motor
M.C.A.
M.F.S.
M.C.B
M.C.A.
M.F.S.
M.C.B
Table-19
Electrical Data Unit wiring with electric heater.
LK-0580HC
5
21
25
25
-
-
-
LK-0580CC
10
28
35
35
-
-
-
LK-0880HH
9
32.5
45
45
35.5
45
45
LK-0880CH
18
45
60
60
48
60
60
36
58
70
70
61
70
70
9
42.5
45
45
-
-
-
LK-1080HH
18
55
60
60
-
-
-
36
68
70
70
-
-
-
9
40.5
45
45
-
-
-
LK-1080CH
18
52
60
60
-
-
-
36
65
70
70
-
-
-
LK-1580CH
18
58
70
70
60
70
70
36
71
90
90
73
90
90
LK-1580HH
18
58
70
70
60
70
70
36
71
90
90
73
90
90
LK-2080HH
36
72
90
90
77
90
90
Tons
MODEL
Unit Operating
Voltage Range
Standard indoor fan motor
Oversized indoor fan motor
M.C.A.
M.F.S.
M.C.B
M.C.A.
M.F.S.
M.C.B
Note: Heater kW ratings are at 380/415 V unit.
3Ø,380/415V,
50Hz
3Ø,380/415V,
50Hz
3Ø,380/415V,
50Hz
3Ø,380/415V,
50Hz
3Ø,380/415V,
50Hz
3Ø,380/415V,
50Hz
3Ø,380/415V,