eleCtriCal data
Nominal
Tons
Unit Model No. Hertz Voltage
Voltage
Range
(Min. to Max.)
MCA
MOP Compressor
Quantity
Compressor
Motor RLA
(Cooling)
Condenser Fan Motor(s)
Condenser
Fan Quantity.
Condenser Fan
Motor FLA
2
LUU247HV
60 208 - 230
187 - 253
18.1
30
1
13.5
1
0.6
3
LUU367HV
24.5
40
1
18.0
2
0.6 x 2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded down
to the nearest standard fuse size.
Table 3: Electrical Data.
electrical data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
10 | duct (HIgH StatIc)
Ceiling-Concealed Duct (High Static) System Engineering Manual