30
4.4 Technical Parameters
Technical Data
LGES-5048*
8
Battery Input Data
Battery Type
*1
Li-Ion
Nominal Battery Voltage (V)
48
Battery voltage range (V)
40~60
Max. Charging Voltage (V)
≤60 (Configurable)
Max. Charging Current (A)
*1
100
Max. Discharging Current (A)
*1
100
Max charge power (W)
4600
Max discharge power (W)
4600
Nominal Battery Capacity (Ah)
126~252
Charging Mode for Li-Ion Battery
Self-adaption to BMS
PV String Input Data
Max. DC Input Power without battery (W)
6500
Max. DC Input Power with battery (W)
7500
Max. DC Input Voltage (V)
580
MPPT Range (V)
125~550
Start-up Voltage (V)
125
Min. Feed-in Voltage(V)
*2
150
MPPT Range for Full Load (V)
215~500
Nominal DC Input Voltage (V)
360
Max. Input Current (A)
11/11
Max. Short Current (A)
13.8/13.8
Max. Backfeed Current to The Array (A)
0
No. of MPP Trackers
2
No. of Strings per MPP Tracker
1
AC Output Data (On-grid)
Nominal Apparent Power Output to Utility Grid
(VA)
*7
5000
Max. Apparent Power Output to Utility Grid (VA)
*3
5000
Nominal Apparent Power from Utility Grid (VA)
9200